EMS 5000 FIREPOINT

10. To set up Mimics/Repeaters on the system:

Before any slave panels can be changed to mimic panels it is essential that the network
is communicating with the slave panels.
This is required due to messages being sent across the network to configure the mimic
function. It is therefore essential that all nodes are online.
If there are any nodes that are offline, these will be stated on the main screen as a fault.
Any offline nodes will need to be re-onlined.
Up to three mimic/repeater panels are allowed on each system. To change panel(s) to
have this functionality, at the main panel: -
Access the Main menu. Scroll down to Fire DB and press the "YES" key. Now scroll down
the menu until you reach Mimic and press the "YES" key. Now while within the Mimic
menu simply scroll down to the "LAN nodes" you want to change to Mimics. ("LAN
nodes" are listed after the "BUS nodes").
Once found press the "YES" key to change their status from 'OFF' to 'ON'.
NOTE: Only change the settings of the "LAN nodes" as the "Bus nodes" are for
nodes with H/W connections. "LAN nodes" are for Radio LAN nodes, which are
used for this mimic application.
This process can be followed for up to three nodes.
The selected nodes will now be set as mimics. You can now exit the menu and return to
the main screen.
©2015 EMS Security Group Ltd. All rights reserved.
TSD234 Iss 3 25/06/15 AJM