Tvm; Phase Reversal - ABB WVM Series Selection Manual

Voltage monitors
Table of Contents

Advertisement

US Patent 6541954
ANSI Device #27/47/59
Protects Against: Phase
Loss, Phase Reversal,
Under, Over, and
Unbalanced Voltages,
Short Cycling
Fixed Trip Points and
Delays
Fixed Voltages from 208
.. 480 V AC
Isolated 10 A, SPDT
Relay Contacts
Bi-color LED Indicator
Shows: Output Status,
Faults, Time Delays and

Phase Reversal

ASME A17.1 rule 210.6
NEMA MG1 14:30, 14:35
IEEE C62.41-1991 Level B
Approvals:
Accessories
Female quick
connect P/Ns:
P1015-13
(AWG 10/12)
P1015-64
(AWG 14/16)
P1015-14
(AWG 18/22)
3-phase fuse
block/disconnect
P/N: FH3P
2 Amp Fuse
P/N: P0600-11
See accessory pages for
specifications.
7.16
1TRC 001 009 C0202
Compact 3 Phase Voltage Monitor
TVM Series The Net
Motor Protector
Description
Provides protection for motors and other sensitive loads. Continuously measures the voltage of each of
the three phases using a new microcomputer circuit design that senses under and over voltage, voltage
unbalance, phase loss, and phase reversal. Protection is provided even when regenerated voltages are
present. Includes a trip delay to prevent nuisance tripping and a restart delay to prevent short cycling after
a momentary power outage.
Operation
Upon application of line voltage, the restart delay
begins. The output relay is de-energized during restart
delay. Under normal conditions, the output energizes
after restart delay. Undervoltage, overvoltage, and
voltage unbalance must be sensed for continuous
trip delay period before the output is de-energized.
The output will not de-energize if a fault is corrected
during the trip delay. The restart delay begins as soon
as the output relay de-energizes. If the restart delay is
completed when the fault is corrected, the output relay
will energize immediately.
The output relay will not energize if a fault or phase
reversal is sensed as three phase input voltage is
applied.
Reset: Reset is automatic upon correction of a fault.
Connection
Relay contacts are isolated. Dashed lines are
internal connections.
F = 2A Fast Acting Fuses are recommended,
but not required.
L1 = Phase A
L2 = Phase B
NO = Normally Open
NC = Normally Closed
C = Common, Transfer Contact
Ordering Table

TVM

X
Series
Line Voltage
–208 A
- 208 V AC
–220 A
- 220 V AC
–230 A
- 230 V AC
–240 A
- 240 V AC
–380 A
- 380 V AC
–400 A
- 400 V AC
–415 A
- 415 V AC
–440 A
- 440 V AC
–460 A
- 460 V AC
–480 A
- 480 V AC
Example P/N:
TVM240A45S10S
TM
LED Operation
The LED flashes green during the restart delay, then
glows green when the output energizes. It flashes
red during the trip delay then glows red when the
output de-energizes. It flashes red/green if phase
reversal is sensed.
LED Flashing Table
Trip Delay
Restart Delay
Phase Reversal
Mechanical View
Inches (Millimeters)
L3 = Phase C
X
X
Voltage Unbalance
Trip Delay
–Specify Fixed Delay
Specify Fixed
In Seconds (S)
Percentage
[0.2
–4, 5, 6, 7, 8,
In 0.1 s Increments
9, or
10
[1
In 1 s Increments
ABB Inc. • 888-385-1221 • Technical assistance 800-377-7722 • www.ssac.com
Red
ON/OFF
115 FPM
Green
ON/OFF
Red/Green
Alternate
115 FPM
FPM = Flashes per minute
X
Restart Delay
–Specify Fixed Delay
In Seconds (S)
[0.5
... 1]
... 1]
In 0.1 s Increments
[1
... 100]
... 100]
In 1 s Increments
In Minutes (M)
[1
... 999]
In 1 M Increments
Low Voltage Products & Systems
57 FPM