ABB WVM Series Selection Manual page 25

Voltage monitors
Table of Contents

Advertisement

Economical Single Phase
Brownout/Undervoltage
Protection
Isolated 8 A SPDT Relay
Contacts
Protects sensitive 110-120 V
AC or 220-240 V AC Loads
Adjustable Low Voltage Trip
Point
LED Indicator
Approvals:
Accessories
Quick connect to
screw adaptor
P/N: P1015-18
Female quick
connect
P/N:
P1015-64
(AWG 14/16)
DIN rail P/N's:
017322005 (Steel)
DIN rail adaptor
P/N: P1023-20
See accessory pages for
specifications.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • Technical assistance 800-377-7722 • www.ssac.com
KVM Series
Single Phase
Undervoltage Monitor
Description
The KVM Series is a single phase undervoltage monitor designed to protect sensitive equipment against
brownout undervoltage conditions. The compact design and encapsulated construction make the KVM an
excellent choice for OEM equipment.
Operation
The output relay is energized and the LED glows
green when the input voltage is above the reset
voltage threshold. If the input voltage drops below the
undervoltage set point, the output relay and LED will
de-energize. The output relay will remain de-energized
as long as the input voltage is below the reset voltage.
Reset is automatic when the input voltage returns to a
normal range.
Connection
V = Voltage L = LED S = Undervoltage Set Point
NO = Normally Open
NC = Normally Closed
C = Common, Transfer Contact
Dashed lines are internal connections.
Undervoltage Set Point (Adjustable)
78 ... 99 V AC
156 ... 199 V AC
Technical Data
Line Voltage
Type
Input Voltage/Frequency
Power Consumption
Power Off Reset Time
Undervoltage Detection
Undervoltage Set Point
Undervoltage Reset Point
Repeatability
Voltage Sensing Accuracy
Output
Type/Form
Rating
Life
LED Indicator
Protection
Surge
Circuitry
Isolation Voltage
Insulation Resistance
Mechanical
Mounting
Package
Termination
Environmental
Operating/Storage Temperature
Humidity
Weight
Function
TP = Undervoltage Set Point
Mechanical View
Inches (Millimeters)
Maximum Line Voltage
132 V AC
264 V AC
Single Phase
110 ... 120 V AC or 220 ... 240 V AC/50 ... 60 Hz
2.5W at 132 V AC; 4.5W at 264 V AC
< 150 ms
KVM4
78 ... 99 V AC
KVM6
156 ... 199 V AC
KVM4
Fixed at 104 V AC
KVM6
Fixed at 209 V AC
+/- 0.5% under fixed conditions
+/-1% over temperature range
+/-2% at 25°C
Electromechanical Relay/SPDT
8 A resistive at 120 V AC, 1/3 hp at 120/240 V AC
Mechanical; 1 x 10
Glows green when output energized
IEEE C62.41-1991 Level A
Encapsulated
> 1500 V RMS Input to Output
> 100 MΩ Minimum
Surface mount with one #10 (M5 x 0.8) screw
2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
0.25 in. (6.35 mm) male quick connect terminals
-25 to +55°C/-40 to +85°C
95% relative, non-condensing
2.6 oz (74 g)
R = Reset Point
Part Number
KVM4
KVM6
6
; Electrical; 1x10
5
1TRC 001 009 C0202
7.25