Tvw - ABB WVM Series Selection Manual

Voltage monitors
Table of Contents

Advertisement

US Patent 6541954
ANSI Device # 27/47/59
Protects Against: Phase
Loss, Phase Reversal, Under,
Over, and Unbalanced
Voltages, Short Cycling
Fixed Trip Points and Delays
Adjustable Voltages from
208 ... 480 V A C
in 4 Ranges
Monitor 600 V AC Lines by
Connecting VRM Accessory
Isolated 10 A, SPDT Relay
Contacts
Bi-color LED Indicator
Shows: Output Status,
Faults, Time Delays, Phase
Reversal and Set Point
ASME A17.1 rule 210.6
NEMA MG1 14:30, 14:35
IEEE C62.41-1991 Level B
Approvals:
Accessories
Female quick connect
P/Ns:
P1015-13
(AWG 10/12)
P1015-64
(AWG 14/16)
P1015-14
(AWG 18/22)
3-phase fuse
block/disconnect
P/N: FH3P
2 Amp Fuse
P/N: P0600-11
See accessory pages for
specifications.
7.14
1TRC 001 009 C0202
Compact 3 Phase Voltage Monitor
TVW Series The Net
Motor Protector
Description
Provides protection for motors and other sensitive loads. Continuously measures the voltage of each of
the three phases using a new microcontroller circuit design that senses under and overvoltage, voltage
unbalance, phase loss, and phase reversal. Protection is provided even when regenerated voltages are
present. Includes a trip delay to prevent nuisance tripping and a restart delay to prevent short cycling after
a momentary power outage.
Operation
Upon application of line voltage, the restart delay
begins. The output is de-energized during restart delay.
Under normal conditions, the output energizes after the
restart delay. Undervoltage, overvoltage, and voltage
unbalance must be sensed for the complete trip delay
period before the output de-energizes. The restart
delay begins as soon as the output de-energizes. If
the restart delay is completed when a fault is corrected,
the output energizes immediately. The output will
not energize if a fault is sensed as the input voltage
is applied. If the voltage selector is set between two
voltage marks (e.g. between 220 and 230 V), the LED
will flash red rapidly. The TVW provides fault protection
at the lower of the two line voltages (e.g. 220 V).
Reset: Reset is automatic upon correction of a fault.
Connection
F = 2 A Fast Acting Fuses are recommended, but
not required.
L1 = Phase A
L2 = Phase B
NO = Normally Open NC = Normally Closed
C = Common, Transfer Contact
Ordering Table

TVW

X
Series
Line Voltage
Wide Range
5
- 208 ... 240 V AC
Selectable
6
- 208, 220, 230 &
240 V AC
8
- 380, 400 & 415 V AC
9
- 430, 440, 460 & 480 V AC
Example P/N:
TVW645S10S
TVW960.2S1M
TM
LED Operation
The LED flashes green during the restart delay, then
glows green when the output energizes. It flashes
red during the trip delay then glows red when the
output de-energizes. It flashes red/green if phase
reversal is sensed. If the voltage selector knob is
between settings, it rapidly flashes red.
LED Flashing Table
Trip Delay
Restart Delay
Phase Reversal
Voltage Selector
Between Marks
Mechanical View
Relay contacts are
isolated. Dashed
lines are internal
connections.
L3 = Phase C
Inches (Millimeters)
X
X
Voltage Unbalance
Trip Delay
Specify Fixed
–Specify Fixed Delay
Percentage
In Seconds (S)
– 4, 5, 6, 7, 8,
In 0.1 s Increments
9, or
10
In 1 s Increments
= 208, 220, 230 & 240 V AC, 4% Voltage Unbalance,
5 Second Trip Delay, 10 Second Restart Delay
= 430, 440, 460 & 480 V AC, 6% Voltage Unbalance,
0.2 Second Trip Delay, 1 Minute Restart Delay
ABB Inc. • 888-385-1221 • Technical assistance 800-377-7722 • www.ssac.com
Red
ON/OFF
Green
ON/OFF
Red/Green
Alternate
Red
ON/OFF
FPM = Flashes per minute
FPS = Flashes per second
X
Restart Delay
–Specify Fixed Delay
In Seconds (S)
... 1]
[0.2
[0.5
... 1]
In 0.1 s Increments
... 100]
[1
[1
... 100]
In 1 s Increments
In Minutes (M)
[1
... 999]
In 1 M Increments
Low Voltage Products & Systems
115 FPM
57 FPM
115 FPM
460 FPM
(7.5 FPS)