Contemporary Controls BASstat BAST-421C-BW2 User Manual page 21

Wireless modulating thermostat
Table of Contents

Advertisement

Item
Mnemonic
E30
tyPE
Control Type
E31
OPL2
Minimum Output for AO2
E32
SPA2
Span Offset for AO2
E33
Hrtr
Communication Heartbeat Minimum Rate
E34
rhPB
Humidity Control PB
E35
rhdF
Humidity Control Diff.
E37
CO2F
CO2 Offset Value
E38
AFtH
After Hour Extension Time (not used)
E39
VALL
Input Low Value of Valve Feedback
(not used)
E40
VALH
Input High Value of Valve Feedback
(not used)
E41
OPts
Options (not used)
E42
dlAb
DI contact Defination (not used)
E43
Hrt
Communication Heartbeat Flip-Flop
E44
CSPL
Minimum Cooling Temperature Setpoint
E45
HSPH
Maximum Heating Temperature Setpoint
E46
nFAn
Minimum Fan Output (not used)
E47
hFAn
Maximum Fan Output (not used)
E48
FAnL
Low Fan Speed Setting (not used)
E49
FAn2
Med. Fan Speed Setting (not used)
E50
FAnH
Hi Fan Speed Setting (not used)
E51
ObAb
Humidity Control PB (not used)
E52
OFFt
Minimum Off Time
E53
On-t
Minimum On Time
E54
It-2
Integral Time and Output Cycle Time 2
E55
Phy1
MAC address 1st & 2nd bytes
E56
Phy2
MAC address 3rd & 4th bytes
UM-15093500-AA1
Description
°C Scale
Default
Range
2
1~2
0(0V)
0~125
0 (0v)
0(0V)
0~125
0 (0v)
60
10~3600
60
0
0/1
18.0
0.0- 50.0
65.0
25.0
0.0-50.0
180
0~600
180
0
0~600
0
60
0~500
60
hhhh
hhhh
°F Scale
Default
Range
1: 4-Pipe
cooling or
heating
Manual
2
1~2
Changeover
2: 4-Pipe
heating and
cooling auto
Changeover
0~125
1 (LSB)
(0.044V)
0~125
1 (LSB)
(0.044V)
10~3600
10s
0
0/1
0: Off
1: On
32.0-122.0
0.1(°C/°F)
77.0
32.0-122.0
0.1(°C/°F)
0~600
5 (seconds)
0~600
5 (seconds)
0~500
10 (Seconds)
hhhh
h: 0~F in hex
hhhh
h: 0~F in hex
Page 20
Step

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BASstat BAST-421C-BW2 and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents