Contemporary Controls BASstat BAST-421C-BW2 User Manual page 20

Wireless modulating thermostat
Table of Contents

Advertisement

Item
Mnemonic
E13
ESI
ESI (DI1) digital sensor contact definition
Modulating Cooling direct/ reverse signal
E14
rE-C
output
Modulating Heating direct/ reverse signal
E15
rE-H
output
Present Temperature is getting from built-in
temperature Sensor, remote temperature
E16
rS
sensor, or assigned through communication
Display present temperature value of or
current set-point for LCD
E17
-SP-
E18
door
Door or Windows contact definition (not
applicable to all models)
E19
LFAn
Lowest Fan speed in Auto fan mode
E20
Pct
Output Percentage (not used)
E21
devH
Device instance no. - Hi bytes
E22
dEUL**
Device instance no. - Low bytes
UdP**
UDP port number
E23
E24
rHSt
Relative Humidity Offset
E25
F-Ht
Fan Output for Heating
E26
dLyC
Cooling Stage Delay
Cooling Maximum Cycles per
E27
cycC
Hour
E28
dLyH
Heating Stage Delay
Heating Maximum Cycles per
E29
cycH
Hour
UM-15093500-AA1
Description
°C Scale
Default
Range
Default
0
0~1
0
0~1
0
0~1
0
0~2
0
0~1
0
0~1
0
0~1
0
0~100
100
0~4194
100
0~999
1
(ifID-H <=
4193)
0~302 ( if ID-
H
= 4194)
47808
0~65535
47808
(BAC0)
(0~FFFF)
(BAC0)
0
0
0/1
3
1~3
4
2~6
3
0~3
4
2~255
°F Scale
Step
Range
0: N.O.
0
0~1
1: N.C.
0
0~1
0 (direct)
1 (reverse)
0
0~1
0 (direct)
1 (reverse)
0: built-in
1: remote sense
0
0~2
2: assigned
through
BACnet
0: display PV
0
0~1
1: display SP
0: N.O.
0
0~1
1: N.C.
0: stop
0
1: low
0~1
0
0~100
1%
0~4194
1
0~999
1
1
(ifID-H
<=4193)
0~302 ( if
ID-H
= 4194)
0~65535
(0~FFFF
)
0
0.1%RH
-30.0~30.0
0: Disable
0
0/1
1: Enable
1 (minutes)
3
1~3
1 (cycles/hour)
4
2~6
1 (minutes)
3
0~3
1 (cycles/hour)
4
2~255
Page 19