12 Specific data IO-Link (pin 6)
12.4.24 Operating Times
The current valve travel times can be read out with the Operating Times parameter.
In-
Sub-
Off-
Access
dex
In-
set
Rights
dex
0x62
1
RO
2
RO
Description of parameter values
Parameter
Operating Time
Open
Operating Time
Close
12.4.25 Positioner parameter
The properties can be set for the Positioner parameter.
In-
Sub-
Off-
Access
dex
In-
set
Rights
dex
0xB0
1
R/W
2
R/W
3
R/W
4
R/W
Description of parameter values
Parameter
Reinforcement P kp
Reinforcement D kD
Derivative action
time T1
Dead zone
(0.1 to 25.0%)
GEMÜ 543
Positioner (Code S0)
Length
Parameter
8 bits
Operating Time
Open
8 bits
Operating Time
Close
Values
0 to 255
Read out current operating time (in tenths of seconds) from end position
0 to 25.5 s
CLOSED to end position OPEN.
0 to 255
Read out current operating time (in tenths of seconds) from end position OPEN
0 to 25.5 s
to end position CLOSED.
Length
Parameter
16 bits
Reinforcement P kp
16 bits
Reinforcement D kD
16 bits
Derivative action
time T1
16 bits
Dead zone
Values
1 to 200
Set the P component of the positioner.
(0.1 to 20.0)
1 to 200
Set the D component.
(0.1 to 20.0)
0 to 100
Set the derivative action time T1 (always available delay constant).
(0 to 100 s)
1 to 250
Set the dead zone (hysteresis).
Type
Default
uint:8
uint:8
Description
Type
Default
uint: 16
uint: 16
uint: 16
uint: 16
Description
48 / 64
Values
0
0 to 255,
0 to 25.5 s
0
0 to 255,
0 to 25.5 s
Values
200
1 to 200
(0.1 to 20.0)
10
1 to 200
(0.1 to 20.0)
0
0 to 100
(0 to 100 s)
10
1 to 250
(0.1 to 25.0%)
www.gemu-group.com