GEM 543 eSyStep Operating Instructions Manual page 44

Code s0
Table of Contents

Advertisement

12 Specific data IO-Link (pin 6)
12.4.16 Logic Digital Inputs/Outputs
The inputs and outputs can be inversed with the Logic Digital Inputs/Outputs parameters.
In-
Sub-
Off-
Access
dex
In-
set
Rights
dex
0x4E
1
0
R/W
2
1
R/W
3
2
R/W
4
3
R/W
Description of parameter values
Parameter
Logic Digital
Input 1
Logic Digital
Input 2
Logic Digital
Input/Output
Logic Digital
Output
12.4.17 Error Action
The safety position can be set with the Error Action parameter.
The safety position is approached when an error occurs, if the supply voltage is too low within the range of 17.8 V to 21.1 V or
in case of the corresponding signal present at Safe/On.
In-
Sub-
Off-
Access
dex
In-
set
Rights
dex
0x4F
1
R / W
2
R / W
Description of parameter values
Parameter
Error Action
Error Time
GEMÜ 543
Positioner (Code S0)
Length
Parameter
1 bit
Logic digital
input 1
1 bit
Logic digital
input 2
1 bit
Logic Digital
Input/Output
1 bit
Logic digital
output
Values
0
(Active high) Input 1 not inversed.
1
(Active low) Input 1 inversed.
0
(Active high) Input 2 not inversed.
1
(Active low) Input 2 inversed.
0
(Active high) Input/output not inversed.
1
(Active low) Input/output inversed.
0
(Active high) Output not inversed.
1
(Active low) Output inversed.
Length
Parameter
2 Bit
Error Action
10 bits
Error Time
Values
0
(Hold) Actuator remains in the current position in case of an error.
1
(Open) Actuator moves to the OPEN position in case of an error.
2
(Close) Actuator moves to the CLOSED position in case of an error.
1 to 1000
Determine delay time between error detection and error message.
Type
Default
Boolean
Boolean
Boolean
Boolean
Description
Type
Default
uint:8
Code S0 /
S5: 2
Code S6: 1
uint:16
1 (0,1s)
Description
44 / 64
Values
0
0
1
0
0
1
0
0
1
0
0
1
Values
0
1
2
1 ... 1000
(0,1s ... 100s)
www.gemu-group.com

Advertisement

Table of Contents
loading

Table of Contents