CD3000S
1PH from 10A to 90A
10

Fuses and Fuse holder

Warning: High speed fuses are only used for the thyristor protection and can not be used to
protect the installation.
CD3000S unit must be protected against short circuit by High speed fuses.
The Fuses must have I²T 20% less than thyristor's I²T.
The warranty of thyristor is null if no proper fuses are used. See tab.
Fuses and Fuse holder Code for CE
Size
Fuse Holder Code
FFH1038
2x10A (S0)
FFH1038
15A (S0)
FFH1038
25A (S0)
FFH1451
35A (S3)
FFH1451
45A (S3)
FFH2258
60A (S7)
FFH2258
90A (S7)
Fuses and Fuse Holder Code for UL (Standard version only)
Size
Fuse Holder Code
FFH1038
2x10A (S0)
FFH1038
15A (S0)
FFH1038
25A (S0)
FFH1451
35A (S3)
FFH1451
45A (S3)
FFH2258
60A (S7)
FFH2760
90A (S7)
Fuse Code
FU1038/16A
FU1038/16A
FU1038/32A
FU1451/40A
FU1451/50A
FU2258/80A
FU2258/125A
200 kA
Symmetrical A.I.C.
RMS
Total Current
Fuse Code
FU1038/16AUL
FU1038/16AUL
FU1038/25AUL
FU1451/40AUL
FU1451/50AUL
FU2258/80AUL
FU2760/125AUL
28
Total Current
2
I
T (A
(A
)
RMS
16
150
16
150
32
600
40
1650
50
2000
80
6550
125
14000
2
2
I
T (A
sec)
(A
)
RMS
16
150
16
150
32
600
40
750
50
1800
80
6600
125
6970
User's manual
Quantity
2
sec.)
for each
phase
2
1
1
1
1
1
1
Quantity
for each
Vac
phase
600
2
600
1
600
1
700
1
700
1
700
1
660