Electric Connections - RIB JOLLY ONE Manual

With patented automatic limit switch
Hide thumbs Also See for JOLLY ONE:

Advertisement

Available languages

Available languages

G
B
ROLLING SHUTTER WITH LENGHT SHAFT OVER 4 m
In this case we suggest to mount 2 JOLLY ONE on the same shaft at the shutter extrimities.
It is necessary to eliminate the limit switch of one of the 2 JOLLY ONE and connect in parallel
the two motors.
JOLLY ONE without limit switches
=
IMPORTANT
3 wires cable to connect the two operators

ELECTRIC CONNECTIONS

These instructions are only valid if the operator is located on the support of the shutter with
the motor facing to the right (as seen from the inside of the building).
CAUTION: If the operator is assembled with the motor facing to the left (as seen from the
inside of the building), the movements of the operator and therefore of the run stops are
reversed.
Practically C1 becomes the opening run stop and C2 becomes the closing run stop - OPEN
closes and CLOSE opens.
Initial state - as supplied by the factory
C1 = Closing run stop
C2 = Opening run stop
C1 and C2 must both rest against Seger rings S1 and S2 assembled on the screw of the
run stop.
The switch must be in the INS position.
Unscrew the run-stop cover using a small Philips screwdriver.
IMPORTANT: Before fixing the two pulleis to the shutter laminate (4),
verify that the sense of rotation of the 2 JOLLY ONE is the same.
SPRINGS
26
JOLLY ONE with limit switches
=
IMPORTANT