Operation Programme; Normal Operation With Preheating - Riello G30 MRBLU BF Installation, Use And Maintenance Instructions

Light oil burners
Table of Contents

Advertisement

Available languages

Available languages

8.8

Operation programme

8.8.1

Normal operation with preheating

Yellow
Flame loss during operation (Recycle max 3 attempts)
MV = still
Yellow
Signal not required
D7230
t1
Waiting time of a control box input signal: reaction time,
the control box stands still for the time t1.
t1I
Presence of extraneous light before the heat request: if
the presence of light during the t1l time, a block follows.
t2
Wait time after a request for heat:
the control box stays still for the t2 time.
t2I
Presence of extraneous light during the oil preheating:
if the presence of light lasts the t2l time, a block follows.
t2p
Maximum preheating time: if the thermostat K does not
make the switch within the time t2p a block follows, the
control box remains still for the time t2p.
t3
Pre-purging time
start of the fan motor.
t3I
Presence of an extraneous light during pre-purging.
immediate block.
20011757
Operation
Green
Green
Yellow
Yellow
Block
Green
Yellow
Yellow
Fig. 21
Key to lay-out
F
– Flame detector
I
– Ignition transformer
K
– Enabling switch thermostat for start up after preheating
LED
– Signal of operation status from reset button
MV
– Fan motor
PH
– Diesel oil heater
TL
– Limit thermostat
V1
– Oil valve
Red
Green + Yellow slow blinking
Green + Yellow fast blinking
Yellow
Green
Green + Yellow medium blinking
Red + Yellow fast blinking
Yellow fast blinking
Operating times
t1
max
t1I
max
t2
-
t2I
max
t2p
max
t3
-
t3I
max
The time is expressed in seconds
ts
Safety time:
if at the end of the ts time there is no flame, a block fol-
lows.
t4i
Transformer turn on time
total turn on time ts + t5i.
t5i
Transformer post- turn on time:
additional turn on time after ts.
t4I
Flame loss in operation:
maximum oil valve drop reaction time, after three recycle
attempts a block follows.
t6
Post-purging time:
additional purging time on the opening of the heat limit
thermostat (TL).
t6I
Presence of an extraneous light during post-purging. if
the presence of light lasts the t6l time, a block follows.
t7
Long pre-purging time
pre-purging time more than t3.
20
GB
1
ts
30
t4i
3
t5i
30
t4I
600
t6
15
t6I
1
t7
-
5
-
8
-
3
max
1
max
360
max
30
-
120