The "low temperature cut-off" setting is by default disabled. When enabled, a low cut off temperature can be set. The default
temperature is 5°C, this is a suitable temperature setting for lithium iron phosphate (LFP) batteries. However, always check with
the lithium battery supplier to find out what this temperature should be set at.
The "low temperature cut-off" mechanism will stop battery charging when the battery temperature has dropped below the low
temperature cut-off setting. Battery charging will resume once the battery temperature has risen 0.5°C above the low temperature
cut-off setting.

5.2.2. Load output settings

These settings are typically used to drive the load output.
Make sure that the
remain removed thereafter. If the jumper is not removed, and the
communication" and/or the
jumper will override the VictronConnect load output settings.
Be aware that the load output behaviour will be different than expected when the
enabled (disabled by default).
The load output settings can also be used to drive the TX pin in the VE.Direct port, which can then be used to drive a
BatteryProtect, a relay or an other load-shedding device. For more information see chapter
The available operation modes are:
• Always off
The load output is always OFF
• BatteryLife algorithm:
This is a self adapting algorithm to maximize life of the battery. For more information see chapter
• Conventional algorithm 1:
12V system: OFF when Vbatt < 11.1V, ON when Vbatt > 13.1V
24V system: OFF when Vbatt < 22.2V, ON when Vbatt > 26.2V
48V system: OFF when Vbatt < 44.4V, ON when Vbatt > 52.4V
• Conventional algorithm 2:
12V system: OFF when Vbatt < 11.8V, ON when Vbatt > 14.0V
24V system: OFF when Vbatt < 23.6V, ON when Vbatt > 28.0V
48V system: OFF when Vbatt < 47.4V, ON when Vbatt > 56.0V
• Always on:
The load output is always ON
• User defined algorithm 1:
OFF when Vbatt < Vlow, ON when Vbatt > Vhigh.
• User defined algorithm 2:
OFF when Vbatt < Vlow or Vbatt > Vhigh and ON when Vbatt is between Vlow and Vhigh.
Page 21
MPPT solar charger manual
jumper link [14]
is removed before configuring the load output. The jumper link should
RX [25]
is configured as "load output config" (these are the default settings), the
TX port [24]
is configured as "normal
streetlight settings [22]
TX port settings
[24].
BatteryLife [7]
Configuration and settings
is