SPARE PARTS IN THE REPAIR OF THE EQUIPMENT. THE SPECIFIED MAINTENANCE INTERVALS AS WELL AS THE INSTRUCTIONS FOR REPAIR Mounting AND EXCHANGE MUST BE STRICTLY ADHERED TO PREVENT INJURY TO feet for fixed mounting PERSONNEL AND DAMAGE TO THE EQUIPMENT. Shroud Figure 1. Front connect breaker EATON www.eaton.com...
Page 4
Step 2 Secondary Terminal contact block With the screws removed, pull out the front of the arc hood and set shield assembly it aside (Figure 4) . Front terminal load shield Figure 6. Step 4 Figure 4. Step 2 EATON www.eaton.com...
Page 5
. m CAUTION Figure 7. Step 5 MAKE SURE THE PHASE BARRIERS FROM STEP 6.5 ARE PROPERLY INSTALLED BEFORE PLACING THE CIRCUIT BREAKER INTO SERVICE. FAILURE TO FOLLOW THESE REQUIREMENTS COULD RESULT IN EQUIPMENT DAMAGE AND/OR FAILURE. EATON www.eaton.com...
Page 6
Type NF bus extension kit for 65 kA Effective February 2016 fixed front connect breaker Figure 8. Assembly view (refer to only the line side for this kit) Figure 9. Assembly view (refer to only the line side for this kit) EATON www.eaton.com...
Page 7
Figure 11. Cable terminal kit otee: Terminals sold separately . NOTICE TA1201NB1 (M) [3] 500 – 750 (300) CU/AL (42) 66B2638H01 Figure 14. Step 7.2—Cable terminals connected onto bus extensions on both line and load side Figure 12. Cable terminals torque requirements EATON www.eaton.com...
ANY CONTRACT BETWEEN THE PARTIES . in Figure having a minimum tensile strength of 2000 pounds at In no event will Eaton be responsible to the purchaser or user in 6 inches from terminals and every contract, in tort (including negligence), strict liability or otherwise...
Need help?
Do you have a question about the NRX Series and is the answer not in the manual?
Questions and answers