Technical Data - S+S Regeltechnik THERMASGARD ALTM1 Series Operating Instructions, Mounting & Installation

Surface contact/tube contact temperature measuring transducers, including strap, calibratable, with multi-range switching and active output
Hide thumbs Also See for THERMASGARD ALTM1 Series:
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 6
G
®
THERMASGARD
Calibratable surface-contact temperature measuring transducer THERMASGARD
eight switchable measuring ranges, continuous output, in an impact-resistant plastic housing with quick-locking screws, optionally with ⁄ without
display, cable sensor with a pipe feeder (ALTM 2), incl. strap.
The surface-contact sensor is used to detect the temperature on lines, pipes (e.g., cold and warm water) or on heating sections for heating control.
The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

TECHNICAL DATA

Power supply:
24 V AC ⁄ DC (± 10 %) for U variant
15...36 V DC for I variant, depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance:
R
a
Load resistance:
R
L
Power consumption:
< 1.0 VA ⁄ 24 V DC; < 2.2 VA ⁄ 24 V AC
Sensor:
Pt1000, DIN EN 60751, class B (Perfect Sensor Protection)
Measuring ranges:
multi-range switching with 8 switchable measuring ranges, see table (other ranges optional)
with manual zero point correction (± 10 K)
ALTM 1: compact variant,
ALTM 2: detached sensor variant, T
Deviation, temperature:
typically ± 0.2 K at +25 °C
Output:
0 - 10 V or 4...20 mA
Ambient temperature:
measuring transducer –30...+70 °C
Connection type:
2- or 3-wire connection
Process connection:
endless metal strap and metal tightener (included in the scope of delivery)
Strap dimensions:
Ø = 13 - 92 mm (¼ - 3"), length L = 300 mm
Housing:
plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced, with quick-locking screws (slotted ⁄ Phillips head
combination), colour traffic white (similar to RAL
housing cover for display is transparent!
Housing dimensions:
72 x 64 x 37.8 mm (Tyr 1 without display)
72 x 64 x 43.3 mm (Tyr 1 with display)
Connection cable:
ALTM 2: silicone, SiHF, 2 x 0.25 mm², KL = 1.5 m (other lengths
and range limits optional, e.g. PTFE leads up to +250 °C or glass
fibre with steel wire mesh up to +350°C)
Cable connection:
cable gland, plastic (M 16 x 1.5; with strain relief,
exchangeable, inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on
request)
Electrical connection:
0.14 - 1.5 mm² via terminal screws
Insulating resistance:
≥ 100 MΩ, at +20 °C (500 V DC)
Humidity:
< 95 % r. H., non-precipitating air
Protection class:
III (according to EN 60 730)
Protection type:
ALTM 1: IP 65 (according to EN 60 529) Housing tested,
ALTM 2: IP 65 rolled ⁄ stamped humidity-tight
Standards:
CE conformity, electromagnetic compatibility
according to EN 61326, according to EMC directive
2014 ⁄ 30 ⁄ EU
Optional:
Two-line display with illumination, cutout approx. 36 x15 mm
(W x H), for displaying the ACTUAL temperature and the internal
diagnostics (measuring range exceeded, measuring range not
reached, sensor breakage, sensor short circuit)
®
THERMASGARD
ALTM
Type ⁄ WG01
Sensor
ALTM 1
A LT M1- I
Pt1000
A LT M1- I D I S P L AY
Pt1000
A LT M1- U
Pt1000
A LT M1- U D I S P L AY
Pt1000
ALTM 2
A LT M 2 - I
Pt1000
A LT M 2 - I D I S P L AY
Pt1000
A LT M 2 - U
Pt1000
A LT M 2 - U D I S P L AY
Pt1000
Extra charge:
Other ranges optional
Protection type IP 68 (Sensor sleeve watertight compound-filled)
2-wire connecting leads, per running meter (PVC ⁄ silicone)
Cable connection with M12 connector according to DIN EN 61076-2-101
ACCESSORIES
WLP-1
Heat-conductive paste, silicone-free
ALTM
(ohm) = (U
-14 V) ⁄ 0.02 A for I variant
b
> 5 kOhm for U variant
TÜV SÜD, Report No. 713139052 (Tyr 1)
IP 68 (optional sensor sleeve watertight compound-filled)
Surface contact ⁄ tube contact temperature measuring transducers
Output
4...20 mA
4...20 mA
0 -10 V
0 -10 V
4...20 mA
4...20 mA
0 - 10 V
0 - 10 V
®
ALTM 1 (compact variant) and ALTM 2 (detached variant) with
T
up to +100 °C, operating range –50...+100 °C
max
over +100 °C, operating range –50...+150 °C
max
9016),,
Type
Compact
Compact
Compact
Compact
Remote sensor
Remote sensor
Remote sensor
Remote sensor
Display and internal diagnostics
Standard
Measuring range
exceeded
Measuring range
not reached
Sensor
breakage
Sensor
short circuit
Display
Item No.
IP 65
1101- 1112- 0219-920
1101- 1112- 2219-920
1101- 1111- 0219-920
1101- 1111- 2219-920
IP 65
1101- 1122- 0219-920
1101- 1122- 2219-920
1101- 1121-0219- 920
1101- 1121- 2219-920
on request
on request
7100-0060- 1000- 000