6 Electrical installation
X3M
3 On the outdoor unit, connect the LV cable to the appropriate
terminals as shown in the illustration below.
4 Fix the cables with cable ties to the cable tie mountings.
Bypass valve kit necessity
For reversible systems (heating+cooling) in which an external
backup heater kit is installed, the installation of valve kit EKMBHBP1
is required if condensation is expected inside the backup heater.
Installation manual
20
LV
1
2
X15M
EKLBUHCB6W
X5M
1 2
31
28
25
22
19
16
13
10
7
20
23
B (°C DB)
A
Leaving water evaporator temperature
B
Dry-bulb temperature
Relative humidity 40%
Relative humidity 60%
Relative humidity 80%
Example: Given are an ambient temperature of 25°C and a relative
humidity of 40%. If the leaving water evaporator temperature is
<12°C, condensation will occur.
Note: See the psychrometric chart for more information.
To connect the bypass valve kit
The information in this topic supersedes that of the instruction sheet
delivered with the bypass valve kit.
Wires: 3×0.75 mm²
The components of the bypass valve kit are as follows. You only
need B and D.
A
B
1 Integrate components B and D as follows in the system:
31
28
25
22
19
16
13
10
7
26
29
32
C
D
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620239-1 – 2020.06