Riello RL 70 Installation, Use And Maintenance Instructions page 39

Light oil burners
Table of Contents

Advertisement

Available languages

Available languages

4.2.1
Variants
Model
Code
3475034
RL 70
3475035
3475234
RL 100
3475235
3475434
RL 130
3475435
4.2.2
Accessories (optional):
RADIO DISTURBANCEPROTECTION KIT
If the burner is installed in places particularly subject to
radio disturbance (emission of signals exceeding 10 V/m)
owing to the presence of an INVERTER, or in applications
where the length of the thermostat connections exceeds 20
metres, a protection kit is available as an interface between
the control box and the burner.
BURNER
Code
• DEGASSING UNIT
It may occur that a certain amount of air is contained in the light
oil sucked up by the pump. This air may originate from the light
oil itself as a consequence of depressurization or air leaking past
imperfect seals.
In double-pipe systems, the air returns to the tank from the return
pipe; in single-pipe systems, the air remains in circulation causing
pressure variations in the pump and burner malfunctions.
For this reason, we advise installing a degassing unit near the
burner in single-pipe installations.
Degassing units are provided in two versions:
CODE 3010054 without filter
CODE 3010055 with filter
Burner delivery
Light oil pressure
Ambient temperature
Ambient temperature
Light oil temperature
Light oil temperature
Connectors
For burner deliveries higher than 80 kg/h, install two parallel de-
gassing units
Technical description of the burner
Power supply
Length of
electrical
blast tube mm
Three-phase
250
Three-phase
385
Three-phase
250
Three-phase
385
Three-phase
250
Three-phase
385
RL 70 - RL 100 - RL 130
3010386
: max. 80 kg/h
: max. 0.7 bar
: max. 50 °C (without filter)
: max. 40 °C (with filter)
: max. 50 °C (without filter)
: max. 40 °C (with filter)
: 1/4 inch
7
GB
2916076

Advertisement

Chapters

Table of Contents
loading