Installation- and maintenance instruction
B 40 A2.2 RME
LMO
Translation of the original instructions.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the B 40 A2.2 RME and is the answer not in the manual?

Questions and answers

Summary of Contents for Bentone B 40 A2.2 RME

  • Page 1 CR00182 178 157 54-2 2020-08-27 Providing sustainable energy solutions worldwide Installation- and maintenance instruction B 40 A2.2 RME Translation of the original instructions.
  • Page 2 Beispiel Manualer på övriga språk www.bentone.com\nedladdning 352011030141 Serial no. 1234567 Man.Year 2019 Designation BF 1 KS 76-24 eller scanna QR-koden BF 1 Type Model BF 1 KS 76-24 Cap. Min-Max LIGHT OIL 35-90kW 1,25-6,0 cSt 7-14bar Skriv in brännarens artikelnummer som finns på din...
  • Page 3: Table Of Contents

    9.2 Burner will not start after normal use ________________ 37 9.3 Delayed ignition __________________________________ 38 9.4 Noise in pump ___________________________________ 38 9.5 Pump pressure __________________________________ 38 10. Log of flue gas analysis ____________________________ 40 11. Oil burners maintenance instructions _______________ 41 Bentone...
  • Page 4: General Information

    • Burner tubes, fan wheels and air dampers may contain sharp edges. • The surface temperature of the burner’s components can exceed 60 °C. • Caution: The burner has moving parts, and there is risk of crushing injuries. 165 105 85 Bentone...
  • Page 5 - flue gas ducts and combustion air ducts are not blocked - all actuators and control and safety devices are in working order and correctly set • After commissioning - If the gas burner control has a solid red light, contact your installer. Bentone...
  • Page 6 Oil hoses must be of high-quality fluoride rubber or PTFE intended for FAME, B-100 (RME). The hoses must be fitted with fire-retardant sleeves in order to satisfy requirements according to EN-ISO 6806. Bentone...
  • Page 7 Delivery check • Make sure everything is delivered and the goods have not been damaged during transit. • If something is wrong with a delivery, report it to the supplier. • Transport damage must be reported to the shipping company. Bentone...
  • Page 8: Technical Data B 40A2,2

    • Light oil, B10 heating oil/biofuel blend (as defined in DIN V51603-6) and is used for: • Water heating generators • Hot air generators (these require LMO 24 255 C2E) 2.1 Dimensions B 40 Ø B Ø C 172/274/372 B 40 * Min. recommended distance to floor. 165 105 34 Bentone...
  • Page 9: Working Field B 40 A2,2

    2.2 Working field B 40 A2,2 8,0-26,5 kg/h 95-310 kW mbar 2.2.1 Electric Specification Burner correspond to IP 20 Type Motor Complete Sound burner B 40 250W 230V 1,7A 230V 3,03A 84 dBA ± 0,5 50Hz 8µF 50Hz Max operating current, see data plate Bentone...
  • Page 10: Recommended Nozzle And Pressure

    80° Solid/semisolid Pump pressure 10 bar (8-25 bar) depending on pump model 2.5 Burner installation 2.5.1 Hole patten Make sure the hole pattern on the boiler is designed for burner flange. Combustion device B 40 ø 115 (130) ø 200-250 Bentone...
  • Page 11: Nozzle Table

    89,36 1060 93,70 1111 97,88 1161 101,85 1208 1039 26,00 96,81 1148 101,50 1204 1035 106,04 1258 1081 110,33 1308 1168 The table applies to oil with a viscosity of 4.4 mm /s at a density of 830 kg/m Bentone...
  • Page 12 1057 1267 1089 24,00 1254 1078 1297 1116 1341 1153 1382 1188 26,00 1359 1168 1406 1209 1453 1249 1497 1287 The table applies to oil with a viscosity of 4.4 mm /s at a density of 830 kg/m Bentone...
  • Page 13: Description B 40

    Nozzle assembly 12. Solenoid valve, safety valve 20. Connecting pipe Stage 2 21. Solenoid valve 1 Ignition cable 13. Motor Ignition transformer 14. Nozzle assembly adjustment 22. Solenoid valve 2 Reset button 15. Blast tube Electric panel 16. Damper motor Bentone...
  • Page 14: General Instructions

    The system must be fine-tuned at start-up. The temperature in the chimney must be at least 60 °C at 0.5 m down in the chimney to prevent condensation. 165 105 03 Bentone...
  • Page 15: Installation

    4. Installation 4.1 Handling and lifting instruktion The lifting aid are available as spare parts, Bentone...
  • Page 16: Acceptance Inspection

    • The connection should be made in accordance with the wiring diagram. • Fuse rating is as required If any electrical connection is used other than that recommended by Bentone, there may be a danger of damage to property and personal injury.
  • Page 17: Mount The Burner On The Boiler

    Once the burner has been installed and commissioned, the seals of the various coupling elements should be checked (A). When a leak is detected, it is usually sufficient to tighten the coupling element that is leaking. 165 105 46 Bentone...
  • Page 18: Air Adjustment With Damper Motor

    Reset the control switch to High Load and make sure the correct air quantity exchange of damper motor. is reached. Solenoid valve High capacity (black) High capacity (red) Low capacity (orange) Closed damper (blue) Releasing button N.B. The upper position is the standard position 165 105 05 Bentone...
  • Page 19: Examples Of Basic Setting B 40A2,2

    These are the default settings and controlling the combustion will take place during operation. Selection of power and connection between the different power stages must be selected and adjusted so that the system achieves good functionality 165 105 33 Bentone...
  • Page 20: Setting Values For Nozzle Assembly And Air Damper B 40

    See under Basic settings Note that it is simply a matter of a basic setting that should be adjusted retrospectively once the burner has started. A flue gas analysis and soot quantity measurement must be carried out when fine-tuning the burner. Bentone...
  • Page 21: Burner Servicing

    Close the boiler / spectacle flange. nozzles. Do not Turn on the main power. clean. Check combustion*. Note: When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. 165 305 24 Bentone...
  • Page 22: Servicing Air Dampers

    Make sure the damper axle is properly mounted. Install the intake grille for the air intake. Release the damper motor release button. Check/adjust the combustion. Note: When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
  • Page 23: Replacement Of Damper Motor

    Install the new damper motor on the mounting plate. Connect the damper motor’s cables. Re-install the damper motor and mounting plate on the air intake according to the instructions on servicing the air damper. Turn on the mains power. Check/adjust the combustion. Bentone...
  • Page 24: Servicing The Fan

    Disconnect the motor’s electrical cable Remove the motor Remove the drive shaft and drive coupling from the motor Disconnect the drive coupling from the pump Fit the coupling, pump, and motor. Make sure the drive shaft is connected correctly at both ends Bentone...
  • Page 25: Replacement Of Oil Pump

    Bleed the pump, start the burner and set the correct oil pressure (refer to technical data for correct output). Check combustion.* Note: When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
  • Page 26: Check Oil Line Seals

    • Make sure that no oil seeps from any of the nozzles. If oil seeps out from the nozzle, the solenoid valve is leaky. Use Loctite 5188 on threaded oil pipelines Note: When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
  • Page 27: Instructions Pump

    10 - 28 bar Rated voltage of coil: 220/240V 50/60 Hz Oil temperature: max 90°C Components Suction   Return and internal by-pass plug Nozzle outlet Pressure gauge port Vacuum gauge port Pressure adjustment     165 105 41 Bentone...
  • Page 28 : the by-pass hole of the nozzle plug allows air to pass to the nozzle line without opening of the regulator valve. For the first start up, bleeding can be accelerated by loosening the plug in a pressure gauge port. system Bentone...
  • Page 29 (D-H) max. = 4,5 m 150 150 139 150 108 150 150 150 150 **Q = pump capacity @ 0 bar / Pumpenleistung bei 0 bar Two pipe lift system capacité de l'engrenage à 0 bar/portata della pompa a 0 bar. Bentone...
  • Page 30 5 min. (a condition is that the pump is being lubricated during operation). The tables state the total suction line length in metres at a nozzle capacity of 9,5 Gph. Max. permissible pressure at the suction and pressure side is 2,0 bar. Bentone...
  • Page 31 Mount new gasket and filter Refit the cover Open the oil supply Start the burner and check seals and combustion Note: When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
  • Page 32 Pressure regulator kit 10 - 28 bars No cut-off” piston + short nozzle plug Shaft seal kit (lip seal + protective cone) By-pass plug G 1/4 gasket G 1/4 steel plug G 1/4 plastic plug Filter 10. Cover gasket Bentone...
  • Page 33: Replacement Of Electrical Components

    Turn on the mains power. Check the function of the new component. Start the burner. Check combustion.* Note: When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. 165 105 11 Bentone...
  • Page 34: Oil Burner Control

    8. Oil burner control 8.1 Wiring diagram 165 305 25 Bentone...
  • Page 35: List Of Components

    Reaction time on flame failure: < 1 s < 1 s Ambient temperature: -5 +60°C -20 - +60°C Min. current with flame established: 45 µA dc 45 µA dc Max. photo current at start: 5,5 µA dc 5,5 µA dc Bentone...
  • Page 36: Colour Codes Lmo14/24

    If the reset button is instead kept pressed a second time for at least 3 seconds, you can, via an interface, obtain the corresponding information on a computer or flue gas analyser. To return to normal operation: Press the reset button for 1 second Bentone...
  • Page 37: Fault Location

    Check preheater function Preheater temperature too low Adjust the preheater‘s set operating tem- New oil type perature Check that the oil used has the physical parameters that the burner is rated for. If not, change the oil. 165 105 09 Bentone...
  • Page 38: Delayed Ignition

    Change the oil or the pump's oil parameters Pump worn Replace the pump Pump run using impure oil that has worn the Replace pump and install self-cleaning pump out prematurely filter in the oil system Blocked pump filter Check, clean pump filter Bentone...
  • Page 40: Log Of Flue Gas Analysis

    10. Log of flue gas analysis Owner Adresss Tel. no: Installation Tel. no: Boiler Type Make Power Bentone Burner Type Model Serial no. Fuel Step 1 Step 2 Step 3 Draught in fireplace Fan Press mbar Filter smoke number Flue gas temp. °C...
  • Page 41: Oil Burners Maintenance Instructions

    11. Oil burners maintenance instructions General information If the burner starts but does not ignite Keep the boiler room clean. Ensure that the boiler Make an attempt to start the burner. room has permanent fresh air intake. Switch off before Never make close repeated start attempts.
  • Page 44 Enertech AB. P.O Box 309, SE-341 26 Ljungby. www.bentone.se, www.bentone.com...