Installation- and maintenance instruction
B 45 A2.2 RME
LMO24.255C2E
DV 67C
Translation of the original instructions.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the B 45 A2.2 RME and is the answer not in the manual?

Questions and answers

Summary of Contents for Bentone B 45 A2.2 RME

  • Page 1 CR00349 178 134 56-5 2021-08-04 Providing sustainable energy solutions worldwide Installation- and maintenance instruction B 45 A2.2 RME LMO24.255C2E DV 67C Translation of the original instructions.
  • Page 2 1~230V 1,0A 50Hz IP 20 Motor supply MADE IN SWEDEN BY 1. Manualer på övriga språk 1. Manuals in other languages 1. Manualer på andre sprog 2. www.bentone.com\ 2. www.bentone.com\download 2. www.bentone.com\download nedladdning or scan QR-code. eller scan QR-koden. eller scanna QR-koden.
  • Page 3: Table Of Contents

    9.2 Burner will not start after normal use ________________ 37 9.3 Delayed ignition __________________________________ 38 9.4 Noise in pump ___________________________________ 38 9.5 Pump pressure __________________________________ 39 10. Log of flue gas analysis ____________________________ 40 11. Oil burners maintenance instructions _______________ 41 Bentone...
  • Page 4: Safety Information

    • The surface temperature of the burner’s components can exceed 60 °C. • Caution: The burner has moving parts, and there is risk of crushing injuries. • The electrical installation must be professionally carried out in accordance with applicable high voltage regulations, as per Enertech’s recommendations. 165 105 85 Bentone...
  • Page 5 - fl ue gas ducts and combustion air ducts are not blocked - all actuators and control and safety devices are in working order and correctly set • After commissioning - If the gas burner control has a solid red light, contact your installer. Bentone...
  • Page 6 Oil hoses must be of high-quality fluoride rubber or PTFE intended for FAME, B-100 (RME). The hoses must be fitted with fire-retardant sleeves in order to satisfy requirements according to EN-ISO 6806. Bentone...
  • Page 7 Delivery check • Make sure everything is delivered and the goods have not been damaged during transit. • If something is wrong with a delivery, report it to the supplier. • Transport damage must be reported to the shipping company. Bentone...
  • Page 8: Technical Data

    • Water heating generators • Hot air generators (these require LMO 24 255 C2E) 2.1 Dimensions B 45 A2.2 ØC Ø B Ø C 240/340 B 45 * Min. recommended distance to floor. 165 205 67-3 Bentone...
  • Page 9: Working Field B 45 A2.2

    8.6-45.5 kg/h 102-540 kW mbar -1,0 2.3 Electric Specification Burner correspond to IP 20 Type Motor Complete Sound burner 450W 230V B 45 230V 4,63 A 50Hz 84 dBA ± 0,5 dBA 50/60Hz 10µF Max operating current, see data plate. Bentone...
  • Page 10: Setting Of Brake Plate And Air Flow

    Pump pressure 10 bar (8-25 bar) depending on pump model 2.6 Burner installation 2.6.1 Hole patten Make sure the hole pattern on the boiler is designed for burner fl ange. Combustion device B 45 ø (135) 165 ø (200) 224-270 Bentone...
  • Page 11: Nozzle Table

    89,36 1060 93,70 1111 97,88 1161 101,85 1208 1039 26,00 96,81 1148 101,50 1204 1035 106,04 1258 1081 110,33 1308 1168 The table applies to oil with a viscosity of 4.4 mm /s at a density of 830 kg/m Bentone...
  • Page 12 1057 1267 1089 24,00 1254 1078 1297 1116 1341 1153 1382 1188 26,00 1359 1168 1406 1209 1453 1249 1497 1287 The table applies to oil with a viscosity of 4.4 mm /s at a density of 830 kg/m Bentone...
  • Page 13: Description

    Indicator lamp Stage 1 15. Nozzle Ignition electrodes 10. Switch I-II 16. Pump Gejder 11. Indicator lamp Stage 2 17. Air intake Damper motor 12. Valve Stage 1 18. Air damper Electric box 13. Valve Stage 2 19. Safety valve Ignition transformer Bentone...
  • Page 14 13 12 Bentone...
  • Page 15: General Instructions

    The system must be fine-tuned at start-up. The temperature in the chimney must be at least 60 °C at 0.5 m down in the chimney to prevent condensation. 165 105 65 Bentone...
  • Page 16: Installation

    4. Installation 4.1 Handling and lifting instruktion The lifting aid are available as spare parts. Bentone...
  • Page 17: Acceptance Inspection

    • The connection should be made in accordance with the wiring diagram. • Fuse rating is as required. If any electrical connection is used other than that recommended by Bentone, there may be a danger of damage to property and personal injury. Bentone...
  • Page 18: Mount The Burner On The Boiler

    Once the burner has been installed and commissioned, the seals of the various coupling elements should be checked (A). When a leak is detected, it is usually suffi cient to tighten the coupling element that is leaking. 165 205 68 Bentone...
  • Page 19 4.7.1 Proposed pipe routing for oil distribution systems without transport pump Oil fi lter 4.7.2 Proposed pipe routing for oil distribution systems with transport pump Transport oil fi lter Oil fi lter Overfl ow valve 0.5 – 2.0 bar 1 Transport oil pump / Transportoljepump Bentone...
  • Page 20: Setting Damper Motor 2-Stage

    90° to increase airfl ow. • Return the control switch to position I (low load) and check the combustion values. Solenoid valve High load (black) High load (red) Low load (orange) Closed air damper (blue) Release button 172 511 14-2 2021-05-03 Bentone...
  • Page 21: Examples Of Basic Setting B 45 2.2

    These are the default settings and controlling the combustion will take place during operation. Selection of power and connection between the different power stages must be selected and adjusted so that the system achieves good functionality. 165 105 63-3 Bentone...
  • Page 22: Setting Values For Nozzle And Air Damper

    Recomended exsess air Grade of Oil Excess air flue gases Max. % CO % CO Lambda 1.2 Light oil, B10 heating oil/ 3–5 ≈12,5 15,4 biofuel blend (as defined in DIN V51603-6) Bentone...
  • Page 23: Burner Servicing

    Close the boiler / spectacle fl ange. nozzles. Turn on the main power. Do not clean. Check combustion. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. 165 305 26 Bentone...
  • Page 24: Servicing Air Dampers

    Fit screws (N) for the mounting plate. Insert the burner and tighten the nuts (H). Fit the grille and turn on the mains power. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
  • Page 25: Replacement Of Damper Motor

    Fit the control arm on the damper motor shaft. It is important that the screw is perpendicular to the plane of the shaft. Remove the damper motor as described in the section on servicing the air damper. Turn on the mains power. Check/adjust the combustion. Bentone...
  • Page 26: Servicing The Fan

    Disconnect the motor’s electrical cable. Remove the motor. Remove the drive shaft and drive coupling from the motor. Disconnect the drive coupling from the pump. Fit the coupling, pump, and motor. Make sure the drive shaft is connected correctly at both ends. Bentone...
  • Page 27: Replacement Of Oil Pump

    Bleed the pump, start the burner and set the correct oil pressure (refer to technical data for correct output). Check combustion. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
  • Page 28: Check Oil Line Seals

    • Disconnect the power supply to the solenoid valves Y1, Y2 and Y3 • Provide power to safety solenoid valve Y1S. • Run the motor and pump. • Make sure that no oil seeps from any of the nozzles. If oil seeps out from the nozzle, the solenoid valve is leaky. Bentone...
  • Page 29: Pump Instruction

    0 to+90°C 6.2 Components Nozzle connection G 1/8” Vacuum manometer connection G 1/4” or G 1/8” Manometer connection G 1/8” Filter Suction line G 1/4” Metal plug G 1/4” Return plug Return line G 1/4” Pressure regulation 165 205 69 Bentone...
  • Page 30 6.2.3 Two-pipe system Conversion to two-pipe system Remove the metal plug (7) G ¼”, fi t the return plug (8) in the return line (9). Return plug are not included in products with one-pipe system, separately sold. 6.2.4 Solenoid valve Bentone...
  • Page 31 ”O”. Note: When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
  • Page 32 The total resistance of these items is such that it can be the Q 46 l/h pump capacity at 0 bar applies. disregarded. In the tables no run longer than 100 m is listed, as experience shows this not to be required. Bentone...
  • Page 33: Replacement Of Electrical Components

    Turn on the main power. Check the function of the new component. Start the burner. Check combustion. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. 165 105 11 Bentone...
  • Page 34: Electrical Equipment

    8. Electrical Equipment 8.1 Wiring diagram LMO24.255 ... 165 205 70 Bentone...
  • Page 35: Function Lmo14/24

    1 are fulfilled. The oil burner control cuts out A red lamp in the control is lit. Press the reset button and the burner re-starts. Bentone...
  • Page 36: Colour Codes Lmo14/24

    If the reset button is instead kept pressed a second time for at least 3 seconds, you can, via an interface, obtain the corresponding information on a computer or flue gas analyser. To return to normal operation: Press the reset button for 1 second. Bentone...
  • Page 37: Fault Location

    Preheater temperature too low Check preheater function New oil type Adjust the preheater‘s set operating temperature Check that the oil used has the physical parameters that the burner is rated for. If not, change the oil. 165 105 09-2 2021-01-21 Bentone...
  • Page 38: Delayed Ignition

    Check that the oil used has the physical parameters that the burner is rated for. If not, change the oil. Temperature of the oil from the tank is too low, increase the temperature of oil from tank Clean the pump filter 165 105 09-2 2021-01-21/2 Bentone...
  • Page 39: Pump Pressure

    Pump worn Replace the pump Pump run using impure oil that has worn the Replace pump and install self-cleaning pump out prematurely filter in the oil system Blocked pump filter Check, clean pump filter 165 105 09-2 2021-01-21/3 Bentone...
  • Page 40: Log Of Flue Gas Analysis

    10. Log of flue gas analysis Owner Adresss Tel. no: Installation Tel. no: Boiler Type Make Power Bentone Burner Serial no. Type Model Fuel Step 1 Step 2 Step 3 Draught in fireplace Fan Press mbar Filter smoke number Flue gas temp. °C...
  • Page 41: Oil Burners Maintenance Instructions

    11. Oil burners maintenance instructions General information If the burner starts but does not ignite Make an attempt to start the burner. Keep the boiler room clean. Ensure that the boiler room has permanent fresh air intake. Switch off before Never make close repeated start attempts.
  • Page 44 Enertech AB. P.O Box 309, SE-341 26 Ljungby. www.bentone.com...