GENERAL INSTRUCTIONS General rules Condensation in chimney Oil supply The installation of an oil burner should A modern burner works with less ex- The oil line should be dimensioned be carried out in accordance with local cess air and often also with smaller in accordance with the pump regulations.
Page 7
GENERAL INSTRUCTIONS Adjustment of nozzle assembly Adjust the nozzle assembly with the adjustment screw D to the desired position. Air adjustment First stage: Set the operating switch (S2) on low capacity (I). Loosen the screw (A) and turn the damper to the position wan-ted.
Page 8
MAINTENANCE OF OIL BURNER Warning: Before doing any service switch off power at the main switch and cut off the oil supply. Service of burner head (alt. A) Service of burner head (alt. B) Note! For maintenance of the brake plate, nozzles, electrodes etc, when using a long design of the burner tube, you have to remove the nozzle assembly...
ELECTRIC EQUIPMENT Oil burner control: LMO24.255 Wiring diagram If the boiler is not equipped with wired contacts,connect the enclosed contacts to terminals X4 and X6 in accordance with wiring diagram. 1N ~ 50/60 Hz 230 V 1(3) 171 435 26 15-01...
Page 10
ELECTRIC EQUIPMENT List of components Oil burner control: LMO24.255 A1 Oil burner control S6 Control thermostat, high/low B1 Photoresistor capacity Fuse S7 Main switch H1 Lamp, low capacity Ignition transformer H3 Lamp, lock-out signal 230 V X1 Connection terminal board K1 Thermal overload protection X2 Earth terminal Max loading K1...
Page 11
ELECTRIC EQUIPMENT Colour codes LMO14/24 When the burner starts, three signal lights in the reset switch indicate the normal sequence, as well as provide indication if something ab- normal is happening in accordance with the following table: Preheater in operation Solid yellow Ignition switched on Flashing yellow...
Page 12
INSTRUCTIONS PUMP TYPE SUNTEC A2L 65C - 75C Technical data One or two-pipe system. Viscosity range: 2-12 mm Pressure range: 8-15 bar Rated voltage of coil: 220/240V 50/60 Hz Oil temperature: max 60°C Components 1. Nozzle outlet G 1/8" Stage 2 2.
Page 13
INSTRUCTIONS PUMP TYPE SUNTEC A2L 65C - 75C Pump operating principle for Solenoid valve 2 (NC) closed Solenoid valve 1 (NC) closed A2L 65C - 75C Solenoid valve 2 Solenoid valve 1 (NC) open (NC) open The SUNTEC A2L oil pump has two nozzle outlets.
FAULT LOCATION Burner fails to start Situation Possible causes Remedies Motor runs Flame instability Burner pre-purges Check nozzle to burner head dimension Incorrect head settings and electrode position Low oil pressure Check oil pressure Flame occurs Excess air Adjust air damper Burner locks out Check that photocell is clean and unobstructed...
Page 21
In that the burner conforms to the above mentioned standards it is awarded the CE mark. Indem der Brenner die obengenannten Normen und Richtlinien erfüllt, erhält der Brenner die CE-Kennzeichnung. Du fait de leur conformité aux directives mentionnées ci-dessus, les brûleurs Bentone bénéficient du marquage CE. Ljungby, Sweden, 150227 (27/02/15) Enertech AB, Bentone Division/ är kvalitetscertifierat enligt/...
Page 22
OIL BURNERS MAINTENANCE INSTRUCTIONS General information If the burner starts but does not ignite Make an attempt to start the burner. Keep the boiler room clean. Ensure that the boiler room has permanent fresh air intake. Switch off before Never make close repeated start attempts. dismantling the oil burner.