Bentone B 45 A2.2H Installation And Maintenance  Instruction
Bentone B 45 A2.2H Installation And Maintenance  Instruction

Bentone B 45 A2.2H Installation And Maintenance Instruction

Hide thumbs Also See for B 45 A2.2H:

Advertisement

Quick Links

178 014 56 2014-11-11
Providing sustainable energy solutions worldwide
Installation- and maintenance instruction
B 45 A2.2H

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the B 45 A2.2H and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bentone B 45 A2.2H

  • Page 1 178 014 56 2014-11-11 Providing sustainable energy solutions worldwide Installation- and maintenance instruction B 45 A2.2H...
  • Page 3 DESCRIPTION Components 1. Flame cone 11. Air intake 19. Fuse 2. Fan housing 12. Air damper 20. Indicating lamp Stage 2 3. Fan wheel 13. Connecting pipe Stage 1 21. Switch I-II 4. Damper motor 14. Connecting pipe Stage 2 22.
  • Page 4: Technical Data

    TECHNICAL DATA Type designation B45A2 Dimensions Length of burner tube Flange Measure B B45A2 B45A2 Output range and nozzles recommended Oil capacity Capacity Recommended nozzle Recommended Pump pressure kg/h Mcal/h Angle Danfoss Monarch B45A2 8,5-45,5 101-540 87-464 45° - 60° S, B R, PLP 14 bar...
  • Page 5 TECHNICAL DATA Dimensions of flange ø134 171 225 34 09-01...
  • Page 6: General Instructions

    GENERAL INSTRUCTIONS General rules Condensation in chimney Oil supply The installation of an oil burner should A modern burner works with less ex- The oil line should be dimensioned be carried out in accordance with local cess air and often also with smaller in accordance with the pump regulations.
  • Page 7 GENERAL INSTRUCTIONS Adjustment of nozzle assembly Adjust the nozzle assembly with the adjustment screw D to the desired position. Air adjustment First stage: Set the operating switch (S2) on low capacity (I). Loosen the screw (A) and turn the damper to the position wan-ted.
  • Page 8 MAINTENANCE OF OIL BURNER Warning: Before doing any service switch off power at the main switch and cut off the oil supply. Service of burner head (alt. A) Service of burner head (alt. B) Note! For maintenance of the brake plate, nozzles, electrodes etc, when using a long design of the burner tube, you have to remove the nozzle assembly...
  • Page 9: Electric Equipment

    ELECTRIC EQUIPMENT Oil burner control: LMO24.255 Wiring diagram If the boiler is not equipped with wired contacts,connect the enclosed contacts to terminals X4 and X6 in accordance with wiring diagram. 1N ~ 50/60 Hz 230 V 1(3) 171 435 26 15-01...
  • Page 10 ELECTRIC EQUIPMENT List of components Oil burner control: LMO24.255 A1 Oil burner control S6 Control thermostat, high/low B1 Photoresistor capacity Fuse S7 Main switch H1 Lamp, low capacity Ignition transformer H3 Lamp, lock-out signal 230 V X1 Connection terminal board K1 Thermal overload protection X2 Earth terminal Max loading K1...
  • Page 11 ELECTRIC EQUIPMENT Colour codes LMO14/24 When the burner starts, three signal lights in the reset switch indicate the normal sequence, as well as provide indication if something ab- normal is happening in accordance with the following table: Preheater in operation Solid yellow Ignition switched on Flashing yellow...
  • Page 12 INSTRUCTIONS PUMP TYPE SUNTEC A2L 65C - 75C Technical data One or two-pipe system. Viscosity range: 2-12 mm Pressure range: 8-15 bar Rated voltage of coil: 220/240V 50/60 Hz Oil temperature: max 60°C Components 1. Nozzle outlet G 1/8" Stage 2 2.
  • Page 13 INSTRUCTIONS PUMP TYPE SUNTEC A2L 65C - 75C Pump operating principle for Solenoid valve 2 (NC) closed Solenoid valve 1 (NC) closed A2L 65C - 75C Solenoid valve 2 Solenoid valve 1 (NC) open (NC) open The SUNTEC A2L oil pump has two nozzle outlets.
  • Page 14: Nozzle Table

    NOZZLE TABLE Pump pressure bar kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h 0,40 1,33 1,41 1,49 1,56 0,50 1,66 1,76 1,86 1,95 0,60 2,00 2,12 2,23 2,34 0,65 2,16 2,29 2,42 2,54 0,75 2,49 2,65 2,79 2,93 0,85 2,83 3,00 3,16 3,32...
  • Page 15 NOZZLE TABLE Pump pressure bar kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h 0,40 1,63 1,70 1,76 1,82 0,50 2,04 2,12 2,20 2,28 0,60 2,45 2,55 2,64 2,73 0,65 2,65 2,75 2,86 2,96 0,75 3,08 3,18 3,30 3,42 0,85 3,47 3,61 3,74 3,87...
  • Page 16 NOZZLE TABLE Pump pressure bar kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h 1,00 3,72 3,90 4,08 4,24 1,10 4,09 4,29 4,48 4,67 1,20 4,47 4,68 4,89 5,09 1,25 4,65 4,88 5,10 5,30 1,35 5,02 5,27 5,50 5,73 1,50 5,58 5,85 6,11 6,36...
  • Page 17 NOZZLE TABLE Pump pressure bar kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h 1,00 4,40 4,56 4,71 4,85 1,10 4,84 5,01 5,18 5,34 1,20 5,29 5,47 5,65 5,82 1,25 5,51 5,70 5,89 6,07 1,35 5,95 6,15 6,36 6,55 1,50 6,60 6,83 7,06 7,27...
  • Page 18 NOZZLE TABLE Pump pressure bar kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h 1,00 4,99 5,13 5,26 5,40 1,10 5,49 5,64 5,79 5,93 1,20 5,99 6,16 6,32 6,47 1,25 6,24 6,41 6,58 6,74 1,35 6,74 6,93 7,11 7,28 1,50 7,48 7,69 7,89 8,08...
  • Page 19 NOZZLE TABLE Pump pressure bar kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h 1,00 5,53 5,65 5,77 5,89 1,10 6,07 6,21 6,34 6,47 1,20 6,62 6,77 6,92 7,06 1,25 6,90 7,05 7,21 7,35 1,35 7,45 7,62 7,78 7,94 1,50 8,27 8,46 8,64 8,82...
  • Page 20: Fault Location

    FAULT LOCATION Burner fails to start Situation Possible causes Remedies Motor runs Flame instability Burner pre-purges Check nozzle to burner head dimension Incorrect head settings and electrode position Low oil pressure Check oil pressure Flame occurs Excess air Adjust air damper Burner locks out Check that photocell is clean and unobstructed...
  • Page 21 In that the burner conforms to the above mentioned standards it is awarded the CE mark. Indem der Brenner die obengenannten Normen und Richtlinien erfüllt, erhält der Brenner die CE-Kennzeichnung. Du fait de leur conformité aux directives mentionnées ci-dessus, les brûleurs Bentone bénéficient du marquage CE. Ljungby, Sweden, 150227 (27/02/15) Enertech AB, Bentone Division/ är kvalitetscertifierat enligt/...
  • Page 22 OIL BURNERS MAINTENANCE INSTRUCTIONS General information If the burner starts but does not ignite Make an attempt to start the burner. Keep the boiler room clean. Ensure that the boiler room has permanent fresh air intake. Switch off before Never make close repeated start attempts. dismantling the oil burner.
  • Page 24 Enertech AB. P.O Box 309, SE-341 26 Ljungby. www.bentone.se, www.bentone.com...