Section 2
L2,WHITE; HOT (240V)
WHITE; NEUTRAL (120V)
IMPORTANT: While using the PowerARC 161STH on 120V power, be sure to maintain polarity and use the white wire as the common/neutral,
with the black as the "hot" and the green serving as the ground or damage and malfunction may occur. Do not remove the NEMA 6 -50 plug to
operate on 120V. Use the 240V-120V adapter available from Everlast to adapt the plug to standard 120V power. No other wiring is required.
The unit automatically senses the voltage change and adjusts the output accordingly. The unit is provided with a NEMA 6-50P welder plug for
240V operation. This is a standard 50 amp welder plug with a ground, but no neutral. Care should be exercised when wiring a new plug and
making any modifications to existing wiring. A licensed electrician that is familiar with local wiring codes should be consulted before using,
adding to or making any changes to existing circuits. The information given on the graphic located on the welder supplies the necessary
information for breaker and wire sizing. This information is found in the I1max and the I1eff current input ratings on the graphic. The NEC
supplies special rules on wiring of welder circuits, but local codes and special circumstances may require a heavier or indep endent circuit.
PowerARC 161TH

Wire Connection

GREEN GROUND (120/240v)
RECEPTACLE SIDE
General Setup and Operation
L1,BLACK; HOT(240V)
BLACK; HOT (120V)
50 AMP
EVERLAST
20