Siemens SIMATIC S5 CP 521 Manual page 207

Printer/ascll communications module
Hide thumbs Also See for SIMATIC S5 CP 521:
Table of Contents

Advertisement

CP 521
B.4
Setting the Parameters on the Serial Interface of the CP 521
To establish a point-to-point connection, you must set the ASCII mode parameters
for the serial interface of the CP 521. Store all parameter setting data in DB 1 on a
user submodule (EPROM/EEPROM):
Enter all parameter setting data in DB 1 using the programmer
Transfer DB 1 to two user submodules one after the other
Plug the user submodules into both CP 521s.
Enter the following data for the example program in DB 1 of the user submodule:
Table B-1. Setting the CP 521 Parameters in Interpretive ASCII Mode
Parameter Block Number
: KS = ':0800111';
: KS = ':710050006;
GWA 4NEB 812 6030-02b
Explanation
:0
: Parameter block 0
8
: 9600 baud
0
: Even Parity
0
: No BUSY signal
1
: RS-232-C (V.24) interface
1
:8 Data bits
1
: Handshake ON
:7
: Parameter block 7
1
:Transparent ASCII mode
0050
: Character delay time
50 x 100 ms=5s
006
: Message length 6 bytes
Application Example
B-3