٢.................................... ............................. ...........................................................١. ﺍﺣﺗﻳﺎﻁﺎﺕ ﺍﻟﺳﻼﻣﺔ
٤................................. ................................................................................................. ٢. ﻗﺑﻝ ﺍﻟﺗﺭﻛﻳﺏ
٥................................ .........................................................................................٣. ﺍﺧﺗﻳﺎﺭ ﻣﻭﻗﻊ ﺍﻟﺗﺭﻛﻳﺏ
٦.............................. ........................................... ..............................................٤. ﻣﺳﺎﺣﺔ ﺻﻳﺎﻧﺔ ﺍﻟﺗﺭﻛﻳﺏ
١٠........................... ...............................................................................................٥. ﺍﺣﺗﻳﺎﻁﺎﺕ ﺍﻟﺗﺭﻛﻳﺏ
١٢............................. ................................................................................. ٦. ﺃﻋﻣﺎﻝ ﺗﻭﺻﻳﻝ ﺃﻧﺎﺑﻳﺏ ﺍﻟﺗﺑﺭﻳﺩ
١٩.............................. ...................................................................................................٧. ﺗﻔﺭﻳﻎ ﺍﻟﻬﻭﺍء
٢٠............................. ..................................... ...................................................٨. ﺇﻋﺎﺩﺓ ﻣﻝء ﻏﺎﺯ ﺍﻟﺗﺑﺭﻳﺩ
٢٢.............................. ...........................................................................٩. ﺃﻋﻣﺎﻝ ﺗﻭﺻﻳﻝ ﺍﻷﺳﻼﻙ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ
٢٦........................... ........................................... .......٠١. ﺍﻹﻋﺩﺍﺩ ﻓﻲ ﺍﻟﻣﻭﻗﻊ ﻭﻓﺣﺹ ﺍﻟﻣﻛﻭﻧﺎﺕ ﻗﺑﻝ ﺍﻟﺗﺷﻐﻳﻝ ﺍﻟﺗﺟﺭﻳﺑﻲ
٢٧........................... ........................ ......................................................................... ١١. ﺇﻋﺩﺍﺩﺍﺕ ﺍﻟﻣﻭﻗﻊ
٢٨........................... ......... ...................................................................................... ٢١. ﺍﻟﺗﺷﻐﻳﻝ ﺍﻟﺗﺟﺭﻳﺑﻲ
.ﻋﻧﺩ ﺗﺭﺍﻛﻡ ﻏﺎﺯ ﺍﻟﺗﺑﺭﻳﺩ ﺑﻌﺩ ﺍﻟﺗﺭﻛﻳﺏ ﻓﻲ ﺍﻟﺿﺎﻏﻁ، ﻓﻘﺩ ﺗﻧﺧﻔﺽ ﻣﻘﺎﻭﻣﺔ ﺍﻟﻌﺯﻝ، ﻭﻟﻛﻥ ﺇﺫﺍ ﻛﺎﻧﺕ ﺍﻟﻣﻘﺎﻭﻣﺔ ١ﻣﻳﺟﺎ ﺃﻭﻡ ﻋﻠﻰ ﺍﻷﻗﻝ، ﻓﻠﻥ ﻳﺗﻭﻗﻑ ﺍﻟﺟﻬﺎﺯ
.• ﻗﻡ ﺑﺗﺷﻐﻳﻝ ﺍﻟﺟﻬﺎﺯ، ﻭﺍﺗﺭﻛﻪ ﻗﻳﺩ ﺍﻟﺗﺷﻐﻳﻝ ﻟﻣﺩﺓ ﺳﺕ ﺳﺎﻋﺎﺕ. ﺛﻡ ﺗﺣﻘﻕ ﻟﻣﻌﺭﻓﺔ ﻣﺎ ﺇﺫﺍ ﺍﺭﺗﻔﻌﺕ ﻣﻘﺎﻭﻣﺔ ﺍﻟﺿﺎﻏﻁ ﻟﻠﻌﺯﻝ ﺃﻡ ﻻ
.ﺗﺣﺗﻭﻱ ﻫﺫﻩ ﺍﻟﻭﺣﺩﺓ ﻋﻠﻰ ﻋﺎﻛﺱ ﻟﻠﺗﻳﺎﺭ ﺍﻟﻛﻬﺭﺑﺎﺋﻲ، ﻭﺑﻻﺗﻻﻲ ﻳﺟﺏ ﺍﺳﺗﺧﺩﺍﻡ ﻗﺎﻁﻊ ﺩﺍﺋﺭﺓ ﻳﻣﻛﻧﻪ ﻣﻌﻻﺟﺔ ﺍﻟﺗﻭﺍﻓﻘﻳﺎﺕ ﻟﻣﻧﻊ ﺗﻌﻁﻝ ﻗﺎﻁﻊ ﺍﻟﺩﺍﺋﺭﺓ ﺫﺍﺗﻪ
، ﻳﺟﺏ ﻣﻧﻊ ﺩﺧﻭﻝ ﺃﻳﺔ ﻣﻠﻭﺛﺎﺕ )ﺍﻟﺯﻳﻭﺕ ﺍﻟﻣﻌﺩﻧﻳﺔ ﻣﺛﻝ ﺯﻳﺕ ﻭﺳﻭﺍﺋﻝR410A ﻛﻐﺎﺯ ﺍﻟﺗﺑﺭﻳﺩ. ﺑﻻﻧﺳﺑﺔ ﺇﻟﻰ ﻏﺎﺯ ﺍﻟﺗﺑﺭﻳﺩR410A ١. ﺗﺳﺗﺧﺩﻡ ﻫﺫﻩ ﺍﻟﻭﺣﺩﺓ ﻏﺎﺯ
.( ﺑﻁﺭﻳﻘﺔ ﺃﻛﺛﺭ ﺇﺣﻛﺎ ﻣ ًﺎ. ﺗﺄﻛﺩ ﻣﻥ ﺍﺗﺑﺎﻉ ﺍﻻﺣﺗﻳﺎﻁﺎﺕ ﺍﻟﻭﺍﺭﺩﺓ ﻓﻲ ﺍﻟﻔﺻﻝ ٦-١ ﺍﺣﺗﻳﺎﻁﺎﺕ ﺗﻭﺻﻳﻝ ﺃﻧﺎﺑﻳﺏ ﻏﺎﺯ ﺍﻟﺗﺑﺭﻳﺩSUNISO
٢. ﺗﺑﻠﻎ ﻣﻧﻁﻘﺔ ﺍﻟﺿﻐﻁ ﺍﻟﻌﻻﻲ ﻟﺿﻐﻁ ﺍﻟﺗﺻﻣﻳﻡ ٠٠,٤ ﻣﻳﺟﺎ ﺑﺎﺳﻛﺎﻝ، ﻭﻣﻧﻁﻘﺔ ﺍﻟﺿﻐﻁ ﺍﻟﻣﻧﺧﻔﺽ ١٢,٢ ﻣﻳﺟﺎ ﺑﺎﺳﻛﺎﻝ. ﻛﻣﺎ ﺃﻥ ﺷﺑﻛﺔ ﺃﻧﺎﺑﻳﺏ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ
.٦ ﻫﻲ ﻣﻧﻁﻘﺔ ﻋﻻﻳﺔ ﺍﻟﺿﻐﻁ. ﺍﺳﺗﺧﺩﻡ ﺷﺑﻛﺔ ﺃﻧﺎﺑﻳﺏ ﺩﺍﺧﻠﻳﺔ ﺗﺩﻋﻡ ﺿﻐﻁ ﺍﻟﺗﺻﻣﻳﻡ. ﻟﻼﻁﻼﻉ ﻋﻠﻰ ﻣﻭﺍﺻﻔﺎﺕ ﺷﺑﻛﺔ ﺍﻷﻧﺎﺑﻳﺏ، ﺍﻟﺭﺟﺎء ﺍﻟﺭﺟﻭﻉ ﺇﻟﻰ ﺍﻟﻔﺻﻝ
ﺍﻟﻌﺭﺑﻳﺔ
ﺩﻟﻳﻝ ﺍﻟﺗﺭﻛﻳﺏ
ﻧﻅﺎﻡ ﺍﻟﺗﻘﺳﻳﻡ ﺟﻬﺎﺯ ﺗﻛﻳﻳﻑ ﺍﻟﻬﻭﺍء
ﺍﻟﻣﺣﺗﻭﻳﺎﺕ
. ﻫﻭ ﻏﺎﺯ ﺗﺑﺭﻳﺩ ﻣﺧﺗﻠﻁ. ﻓﺗﺄﻛﺩ ﻣﻥ ﻣﻝء ﺍﻟﻭﺣﺩﺓ ﺑﻐﺎﺯ ﺗﺑﺭﻳﺩ ﺳﺎﺋﻝ ﺇﺿﺎﻓﻲR410A ٣. ﻏﺎﺯ
(.)ﻳﺅﺩﻱ ﻣﻝء ﺍﻟﻭﺣﺩﺓ ﺑﻐﺎﺯ ﺗﺑﺭﻳﺩ ﺇﺿﺎﻓﻲ ﻓﻲ ﺻﻭﺭﺓ ﻏﺎﺯ ﺇﻟﻰ ﺗﻐﻳﻳﺭ ﺗﺭﻛﻳﺏ ﻏﺎﺯ ﺍﻟﺗﺑﺭﻳﺩ ﻭﺇﻋﺎﻗﺔ ﺍﻟﺗﺷﻐﻳﻝ ﺍﻟﻁﺑﻳﻌﻲ
RZQ45LCVAK
RZQ45MUYLK
RZQ48MUYLK
RZR48MUYMK
.ﺳﺗﺭﺗﻔﻊ ﺩﺭﺟﺔ ﺣﺭﺍﺭﺓ ﺍﻟﺿﺎﻏﻁ ﻭﻳﺗﺑﺧﺭ ﻏﺎﺯ ﺍﻟﺗﺑﺭﻳﺩ ﺍﻟﻣﻭﺟﻭﺩ ﻓﻲ ﺍﻟﺿﺎﻏﻁ
.ﺗﺣﻘﻕ ﻣﻥ ﺍﻟﻣﻛﻭﻧﺎﺕ ﺍﻟﺗﻻﻳﺔ ﻟﻠﺗﺄﻛﺩ ﻣﻥ ﻋﻣﻝ ﻗﺎﻁﻊ ﺍﻟﺗﺳﺭﺏ ﺍﻷﺭﺿﻲ
.• ﺗﺄﻛﺩ ﻣﻥ ﺗﻭﺍﻓﻕ ﻗﺎﻁﻊ ﺍﻟﺩﺍﺋﺭﺓ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻣﻊ ﺍﻟﺗﻭﺍﻓﻘﻳﺎﺕ
.R410A ﺗﺄﻛﺩ ﻣﻥ ﺗﻭﺻﻳﻝ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻟﻐﺎﺯ
.ﺭﺍﺟﻊ ﺍﻟﻛﺗﻻﻭﺝ ﻟﻣﻌﺭﻓﺔ ﻁﺭﺯ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺍﻟﺗﻲ ﻳﻣﻛﻥ ﺗﻭﺻﻳﻠﻬﺎ
(.)ﻳﺗﻌﺫﺭ ﺍﻟﺗﺷﻐﻳﻝ ﺍﻟﻁﺑﻳﻌﻲ ﻋﻧﺩ ﺍﻟﺗﻭﺻﻳﻝ ﺑﻭﺣﺩﺍﺕ ﺃﺧﺭﻯ
RZQ20LCVAK
RZQ24LCVAK
RZQ36LCVAK
ﻫﺎﻡ: ﻣﻘﺎﻭﻣﺔ ﺍﻟﺿﺎﻏﻁ ﻟﻠﻌﺯﻝ
.ﺃﻋﻣﺎﻝ ﺗﻭﺻﻳﻝ ﺃﻧﺎﺑﻳﺏ ﺍﻟﺗﺑﺭﻳﺩ
١