Daikin FBQ20EAVAK Installation Manual page 27

Split system air conditioner
Table of Contents

Advertisement

01_EN_3PN06583-10W.fm Page 25 Thursday, March 24, 2011 9:03 AM
With the power on. Troubles can be monitored on the remote controller.
Trouble shooting with the display on the liquid crystal display remote controller.
1. With the wired remote controller. (NOTE 1)
When the operation stops due to trouble, operation lamp flashed, and "
indicated on the liquid crystal display. In such a case, diagnose the fault contents by referring to the table
on the Malfunction code list it case of group control, the unit No. is displayed so that the indoor unit no with
the trouble can be recognized. (NOTE 2)
2. With the wireless remote controller.
(Refer also to the operation manual attached to the wireless remote controller)
When the operation stops due to trouble. the display on the indoor unit flashes. In such a case, diagnose
the fault contents with the table on the Malfunction code list looking for the Malfunction code which can be
found by following procedures. (NOTE 2)
(1) Press the INSPECTION /TEST OPERATION button, "
(2) Press the PROGRAMMING TIME button and find the unit No. which stopped due to trouble.
Number of beeps 3 short beeps
(3) Press the OPERATION MODE SELECTOR button and upper figure of the Malfunction code flashes.
(4) Continue pressing the PROGRAMMING TIME button unit it makes 2 short beeps and find the upper code.
(5) Press the OPERATION MODE SELECTOR button and lower figure of the Malfunction code flashes.
(6) Continue pressing the PROGRAMMING TIME button unit it makes a long beep and find the lower code.
• A long beep indicate the Malfunction code.
NOTE
1. In case wired remote controller. Press the INSPECTION /TEST OPERATION button on remote controller,
"
" starts flashing and changes the inspection mode.
2. Keep down the ON/OFF button for 5 seconds or longer in the inspection mode and the above trouble
history disappears, after the trouble code goes on and off twice, followed by the code "00"(normal).
The display changes from the inspection mode to the normal mode.
12-2 Malfunction code list
• For places where the Malfunction code is left blank, the "
continues operating, be sure to inspect the system and make repairs as necessary.
• Depending on the type of indoor or outdoor unit, the Malfunction code may or may not be displayed.
C
o
d
e
A1
Indoor unit's PC board faulty
A3
Drain water level abnormal
A6
Indoor fan motor overloaded, overcurrent or locked
A8
Indoor unit power supply voltage abnormal
AF
Humidifier faulty
Air cleaner faulty
AH
Only the air cleaner does not function.
Type set improper
AJ
Capacity data is wrongly preset. Or there is nothing programmed in the data hold IC.
Indoor unit fan driver PCB ↔ Indoor control PCB transmission abnormal
C1
Power source malfunction (indoor unit)
C4
Sensor for heat exchanger lamp is fault
C6
Indoor unit fan driver PCB combination failure, control PCB type-wise setting failure
C9
Sensor for suction air lamp is fault
CC
Temperature sensor system faulty
Sensor for remote controller is fault
CJ
The remote controller thermistor does not function, but the system thermo run is possible.
E0
Action of safety device (outdoor unit)
E1
Outdoor unit's PC board faulty (outdoor unit)
English
Perform all the following operations
1 short beep
Perform (3) and (6)
1 long beep
No trouble
" and the Malfunction code are
" is displayed and " 0 " flashes.
" indication is not displayed. Though the system
M
l a
u f
n
t c
o i
n
R /
e
m
r a
s k
26