CAUTION
• If there is any change after airflow adjustment in the ventilation paths (e.g., the duct and air outlet), be sure
to make airflow auto adjustment again.
• Consult your Daikin representative if there is any change in the ventilation paths (e.g., the duct and air
outlet) after the test operation is finished or the air conditioner is moved to another place.
(b) Select External Static Pressure with Remote Controller
Check that 01 (OFF) is set for the "SECOND CODE NO." in "MODE NO. 21" for airflow adjustment on an
indoor unit basis in Table 3. The "SECOND CODE NO." is set to 01 (OFF) at factory set. Change the
"SECOND CODE NO." as shown in Table 4 according to the external static pressure of the duct to be
connected. (1)The "SECOND CODE NO." is set to 01 (an external static pressure of 50 Pa) at
factory set.
Table 4
External Static Pressure
(Pa)
50
60
70
80
90
100
110
120
130
140
150
160
180
200
NOTE
"Mode No." setting is done in a batch for the group. To make or confirm settings for an individual unit, set
the Mode No. shown in parentheses.
CAUTION
Keep in mind that a shortage of airflow quantity or water leakage will result because the air conditioner will
be operated outside the rated range of airflow quantity if the external static pressure is wrongly set.
3. Filter Sign Settings
• The remote controller is provided with an LCD that tells the time of air filter cleaning.
• If the air conditioner is used in places with excessive dust, change the "SECOND CODE NO." as shown
in Table 5. The "SECOND CODE NO." is set to 01 (standard) at factory set.
Table 5
Dirt
Standard
Excessive dust
N
o
d
s i
l p
* Select "No display" under conditions in which the cleaning display is not required, such as the time of regular maintenance.
NOTE
"Mode No." setting is done in a batch for the group. To make or confirm settings for an individual unit, set
the Mode No. shown in parentheses.
English
Thursday, March 24, 2011 9:03 AM
MODE NO.
Note
13 (23)
MODE NO.
Time for display
Approximately
2500 hours
Approximately
1250 hours
y a
(
) *
FIRST CODE NO.
06
FIRST CODE NO.
Note
0
10 (20)
3
SECOND CODE NO.
01
02
03
04
05
06
07
08
09
10
11
12
13
14
SECOND CODE
NO.
01
02
24