Daikin FBQ20EAVAK Installation Manual page 86

Split system air conditioner
Table of Contents

Advertisement

01_EN_3P369976-2C.fm Page 25 Thursday ,October 20, 2016 9:36 AM
〈 Connection information on power supply wiring, earth wiring, and transmission wiring 〉
For the indoor unit wiring and transmission wiring (dash lines in the drawing), follow the instructions in the
indoor unit's installation manual.
V
Branch switch,
overcurrent
breaker
Remote Controller
〈 Specification of standard wiring components 〉
RZ(Q/R)
Minimum circuit amps (MCA)
Recommended field fuse (A)
Power supply wire
diameter(mm²)
NOTES
1. Order appropriate power wire while following national laws and standards for the insulating sheath,
thickness, and length.
2. When installing wiring in a location that can easily come in contact with people, be sure to install an earth
leakage breaker to prevent electric shock.
3. The earth leakage breaker must be a high-speed type breaker of 30mA(<0.1S).
4. Use an earth leakage breaker that can also be used as earth leakage, overload, short-circuit protection.
Be sure to use earth leakage breakers dedicated for earth leakage protection in combination with the load
break switch with fuse or breaker for wiring.
5. RZR48MUYMK is only 50Hz model.
〈 CAUTION 〉
To the electrician
Do not run the unit until the refrigerant piping is complete, as not waiting could break the compressor.
25
POWER SUPPLY
220-240V/230V
1~
50Hz/60Hz
L
N
Earth leakage
breaker
Power supply wire
(60245 IEC 57)
1 2 3
L N
O
U
T
D
O
O
R
U
N
T I
1 2 3
INDOOR UNIT
20
24
18.8
20
2.5 or more
Y
POWER SUPPLY
380-415V/400V
Earth leakage
Branch switch,
breaker
brea
overcurrent
breaker
1 2 3
1 2 3
Remote Controller
V
Y
36
45
45
28.2
16.7
14.9
32
20
2.5 or more
4.0 or more
3N~
50Hz/60Hz
L1 L2 L3
N
Power supply wire
(60245 IEC 57)
L1 L2 L3 N
O
U
T
D
O
O
R
U
N
T I
INDOOR UNIT
48
16
English