Technibel KPAV128C5TAA Technical Data & Service Manual page 13

Table of Contents

Advertisement

Indoor Unit
KPAV128C5TAA
Controller PCB
Part No.
Controls
Control circuit fuse
Remote Control Unit
Fan & Fan Motor
Type
Q'ty ... Dia. and length
Fan motor model ... Q'ty
No. of poles ... rpm (230 V, High)
Nominal output
Coil resistance (Ambient temp. 20°C)
Safety devices
Type
Operating temp.
Run capacitor
Flap Motor
Model
Rating
No. of poles ... rpm
Nominal output
Coil resistance (Ambient temp. 20°C)
Heat Exch. Coil
Coil
Rows
Fin pitch
Face area
mm
W
Open
°C
Close
µF
VAC
W
kΩ
mm
m
2
9
POW-K185GS-N
Microprocessor
250 V 3 A
RCS-5PS3E
Cross-flow
2 ... ø130 / L180
K48407-M01416 ... 1
4 ... 1,160
20
GRY-WHT : 311±7%
WHT-VLT : 97.6±7%
VLT-YEL : 97.6±7%
WHT-PNK : 425±7%
— —
Internal protector
145±5
Automatic reclosing
1.5
440
M2LJ24ZE31
AC 208 / 230 V, 50 / 60 Hz
8 ... 2.5 / 3.0
3 / 2.5
16.45 ± 15%
Aluminum plate fin / Copper tube
2
1.8
0.192
DATA SUBJECT TO CHANGE WITHOUT NOTICE.