11. CHECKING ELECTRICAL COMPONENTS

11-1. Measurement of Insulation
Resistance
The insulation is in good condition if the resistance
exceeds 2MΩ.
11-1-1. Power Supply Wires
Clamp the grounding terminal of the power plug with a
lead clip of the insulation resistance tester and
measure the resistance by placing a probe on either of
the two power terminals. (Fig. 1)
Then, also measure the resistance between the
grounding and other power terminals. (Fig. 1)
11-1-2. Indoor Unit
Clamp an aluminum plate fin or copper tube with the
lead clip of the insulation resistance tester and
measure the resistance by placing a probe on each
terminal screw where power supply lines are
connected on the terminal plate. (Fig. 2)
11-1-3. Outdoor Unit
Clamp an aluminum plate fin or copper tube with the
lead clip of the insulation resistance tester and
measure the resistance by placing a probe on each
terminal screw on the terminal plate. (Fig. 2)
Note that the ground line terminal should be skipped
for the check.
11-1-4. Measurement of Insulation
Resistance for Electrical Parts
Disconnect the lead wires of the desired electric part
from terminal plate, capacitor, etc. Similarly disconnect
the connector. Then measure the insulation resistance.
(Figs. 3 and 4)
NOTE
Refer to Electric Wiring Diagram.
If the probe cannot enter the poles because the hole is
too narrow then use a probe with a thinner pin.
power plug
(Local supply)
probe
NOTE
The shape of the power plug may differ from
that of the air conditioner which you are
servicing.
Clip
Copper
tube or
metallic part
Clip
Copper
tube or
metallic part
Metallic
part
Clip
59
Ground
Insulation
tester
Terminal plate
Insulation
tester
Probe
Insulation
tester
From fan motor,
compressor and
other parts
Probe
Insulation
tester
Fig. 1
Probe
Fig. 2
Fig. 3
Fig. 4