Environment; Mounting; Surge Ground - GE DIAC 66K Instruction Manual

Digital overcurrent relay
Table of Contents

Advertisement

GEK-106261
GEK-106261 5 INSTALLATION
Installation of the relay should be in a clean dry location that is free from dust.
The relay should be securely mounted on a vertical surface that provides accessibility to both the front and rear
of the unit. The outline and panel drilling dimensions are provided in Figure 5–4: DIAC PANEL MOUNTING
AND DRILLING on page 5–5.
The relay should be grounded to the station ground mat with a 12 AWG braided ground lead connected to ter-
minal 4. If the relay is to be retrofitted in a panel, terminal 4 should be removed from the new case and installed
into the old case. For the surge protection to function properly the relay must be grounded.
GE Power Management
DIAC Type 66K Digital Overcurrent Relay
5 INSTALLATION

5.1 ENVIRONMENT

5.2 MOUNTING

5.3 SURGE GROUND

5