These instructions do not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purpose, the matter should be referred to the General Electric Company.
ADJUSTMENTS: STANDARD INSTANTANEOUS UNIT......4-1 TARGETS AND INDICATORS ..............4-2 RESET TARGETS ..................4-3 MANUAL TRIP CIRCUIT TEST ..............4-3 TRIP CIRCUIT ................... 4-3 DIAC 66K COVER INSTALLATION............4-3 RECEIVING, HANDLING, AND STORAGE ..........4-3 4.10 TARGET AND SEAL-IN UNIT ..............4-3 5. INSTALLATION ENVIRONMENT ..................
Page 6
TABLE OF CONTENTS 7. SPECIFICATIONS BURDENS ....................7-1 RATINGS ....................7-2 ENVIRONMENTAL ..................7-2 DIAC Type 66K Digital Overcurrent Relay GE Power Management...
• Fully Retrofittable • Functional separate TOC/IOC, TOC alarm & Standard (EM) IOC operations. • Wide settings range • Drawout case construction † The 66LT curve is used by this relay. GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Same as ‘B’ except one 1 standard hi-set dual range target relay unit (20 to 160 A) Current Rating 1 Amp Nominal Current 5 Amp Nominal Current Revision Level Revision Level DIAC Type 66K Digital Overcurrent Relay GE Power Management...
Section 2.3: RATINGS. The DIAC 66K is packaged in a GE S1 style case. See Figure 5–4: DIAC PANEL MOUNTING AND DRILLING on page 5–5 section for mounting dimensions. The internal connections are shown in Figure 5–1: DIAC TYPE 66K INTERNAL/EXTERNAL CONNECTIONS on page 5–2.
K value equal to the time dial times 250. The minimum value of K is 25 (0.1 × 250) and the The I maximum value is 2475 (9.9 × 250). NOTE: IEC equations are defined by IEC 255-4 and IEEE equations are defined by IEEE PC37.112 DIAC Type 66K Digital Overcurrent Relay GE Power Management...
Page 11
Current Range: 0.5 to 15.9 A (5 Amp Relays) 0.1 to 3.18 A (1 Amp Relays) 5 5 6 7 5 5 6 5 5 6 Multiples of Pickup Setting Figure 2–1: IAC51 TOC CURVE GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Page 12
Current Range: 0.5 to 15.9 A (5 Amp Relays) 0.1 to 3.18 A (1 Amp Relays) 0.01 5 5 6 7 5 5 6 5 5 6 Multiples of Pickup Setting Figure 2–2: IAC53 TOC CURVES DIAC Type 66K Digital Overcurrent Relay GE Power Management...
Page 13
Current Range: 0.5 to 15.9 A (5 Amp Relays) 0.1 to 3.18 A (1 Amp Relays) 0.01 5 5 6 7 5 5 6 5 5 6 Multiples of Pickup Setting Figure 2–3: 55 SHORT TIME TOC CURVES GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Page 14
Current Range: 0.5 to 15.9 A (5 Amp Relays) 0.1 to 3.18 A (1 Amp Relays) 5 5 6 7 5 5 6 5 5 6 Multiples of Pickup Setting Figure 2–4: 57 MEDIUM TIME TOC CURVES DIAC Type 66K Digital Overcurrent Relay GE Power Management...
Page 15
Current Range: 0.5 to 15.9 A (5 Amp Relays) 0.1 to 3.18 A (1 Amp Relays) 5 5 6 7 5 5 6 5 5 6 Multiples of Pickup Setting Figure 2–5: 66 LONG TIME TOC CURVES GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Page 16
Current Range: 0.5 to 15.9 A (5 Amp Relays) 0.1 to 3.18 A (1 Amp Relays) 0.01 5 5 6 7 5 5 6 5 5 6 Multiples of Pickup Setting Figure 2–6: 75 SHORT TIME TOC CURVES DIAC Type 66K Digital Overcurrent Relay GE Power Management...
Page 17
Current Range: 0.5 to 15.9 A (5 Amp Relays) 0.1 to 3.18 A (1 Amp Relays) 0.01 5 5 6 7 5 5 6 5 5 6 Multiples of Pickup Setting Figure 2–7: IAC77 TOC CURVES GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Page 18
Current Range: 0.5 to 15.9 A (5 Amp Relays) 0.1 to 3.18 A (1 Amp Relays) 0.01 5 5 6 7 5 5 6 5 5 6 Multiples of Pickup Setting Figure 2–8: 95 SHORT TIME TOC CURVES DIAC Type 66K Digital Overcurrent Relay GE Power Management...
Page 19
Multiples of Pickup Setting 0.97 0.014 ⋅ ⋅ RESET TIME: ; PICKUP TIME: ----------------- - ----------------------- - 0.02 – – Figure 2–9: IEC INVERSE TOC CURVES GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Page 20
Multiples of Pickup Setting 4.32 1.35 ⋅ ⋅ RESET TIME: ; PICKUP TIME: ----------------- - ------------- - – – Figure 2–10: IEC VERY INVERSE TOC CURVES DIAC Type 66K Digital Overcurrent Relay GE Power Management...
Page 21
Multiples of Pickup Setting 5.82 ⋅ ⋅ RESET TIME: ; PICKUP TIME: ----------------- - ----------------- - – – Figure 2–11: IEC EXTREMELY INVERSE TOC CURVES GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Page 25
Current Range: 0.5 to 15.9 A (5 Amp Relays) 0.1 to 3.18 A (1 Amp Relays) RESET 5 5 6 7 5 5 6 5 5 6 Multiples of Pickup Setting Figure 2–15: DEFINITE TIME GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Page 26
5 5 6 Multiples of Pickup Setting ⋅ ⋅ RESET TIME: ; PICKUP TIME: ----------------- - --------- - – Figure 2–16: I T TIME CURVE DIAC Type 66K Digital Overcurrent Relay GE Power Management...
Page 27
Current Range: 0.5 to 15.9 A (5 Amp Relays) 0.1 to 3.18 A (1 Amp Relays) Multples of Pickup Setting Figure 2–17: IOC CURVE FOR THE HDO INSTANTANEOUS UNIT Figure 2–18: STANDARD (EM) INSTANTANEOUS UNIT GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Page 28
2 PRODUCT DESCRIPTION GEK-106261 Figure 2–19: IOC CURVE FOR THE STANDARD (EM) INSTANTANEOUS UNIT DIAC Type 66K Digital Overcurrent Relay GE Power Management...
When the top of the core is lined up with the calibration stamping, an approximate value of pickup can be determined. Dropout is at least 40 to 50 percent of pickup. GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Page 30
3 CALCULATION OF SETTINGS GEK-106261 DIAC Type 66K Digital Overcurrent Relay GE Power Management...
The DIAC relay consists of a case, cover, support structure, and a connection plug to make up the electrical connection. The case is shown in Figure 6–5: DIAC 66K FRONT AND REAR VIEWS on page 6–9. The exter- nal connections are shown in Figure 5–3: TYPICAL EXTERNAL CONNNECTIONS FOR MOTOR PROTEC- TION on page 5–4.
If damage occurred during shipment a damage claim should be filed at once with the transportation com- pany, and the nearest GE sales office should be notified. If the relay is not installed immediately, it should be stored in its original carton in a location that is dry and protected from dust, metallic chips and severe atmo- spheric conditions.
Page 34
4 HARDWARE DESCRIPTION GEK-106621 0.2 A SETTING 2 A SETTING 0.2 A SETTING 0.2 A SETTING Figure 4–2: OPERATING COIL TAPPED AT 2A (FACTORY DEFAULT) DIAC Type 66K Digital Overcurrent Relay GE Power Management...
4. If the relay is to be retrofitted in a panel, terminal 4 should be removed from the new case and installed into the old case. For the surge protection to function properly the relay must be grounded. GE Power Management DIAC Type 66K Digital Overcurrent Relay...
5 INSTALLATION GEK-106261 5.4 INTERNAL/EXTERNAL CONNECTIONS Figure 5–1: DIAC TYPE 66K INTERNAL/EXTERNAL CONNECTIONS DIAC Type 66K Digital Overcurrent Relay GE Power Management...
Page 37
S H O R T F I N G E R For high range operation, connect B and D to terminal no. 6 and A and C to terminal no. 4 Figure 5–2: IAC TYPE 66K INTERNAL CONNECTIONS DIAGRAM (FOR REFERENCE) GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Page 38
5 INSTALLATION GEK-106261 Figure 5–3: TYPICAL EXTERNAL CONNNECTIONS FOR MOTOR PROTECTION DIAC Type 66K Digital Overcurrent Relay GE Power Management...
FOR SEMI-FLUSH MOUNTING FOR SURFACE MOUNTING FRONT VIEW FRONT VIEW CASE 5/16-18 STUD 76MM VIEW SHOWING ASSEMBLY OF HARDWARE FOR SURFACE MTG. ON STEEL PANELS Figure 5–4: DIAC PANEL MOUNTING AND DRILLING GE Power Management DIAC Type 66K Digital Overcurrent Relay...
5 INSTALLATION GEK-106261 5.6 MOTOR PROTECTION CHARACTERISTIC CURVE Figure 5–5: MOTOR PROTECTION CHARACTERISTIC CURVE DIAC Type 66K Digital Overcurrent Relay GE Power Management...
A relay may be tested without removing it from the panel by using the appropriate test plug. For an S case use the XLA series test plug, refer to the GE Power Management Product Catalog, Prod- ucts CD, or website (the URL is www.ge.com/indsys/pm).
Successively apply currents of 2, 5, and 10 times pickup TOC, verifying that the operating times are within the margins indicated in Table 6–1: PICKUP TIMES FOR VARYING MULTIPLES OF PICKUP (MPU) DIAC Type 66K Digital Overcurrent Relay GE Power Management...
PICKUP VERIFICATION • Connect the relay as indicated in Figure 6–2: DIAC 66K TOC INVERSE TIME TEST SETUP. In order to apply current to the relay, use a 50/60 Hz voltage source, with a variable resistor in series, or an electronic current source.
VARYING MULTIPLES OF PICKUP (MPU) on page 6–3. With the relay still connected as indicated in Figure 6–2: DIAC 66K TOC INVERSE TIME TEST SETUP, set the time overcurrent unit to minimum pickup and set the corresponding time dial to 5. Enable the Instantaneous HDO settings by setting the pickup to the lowest setting (not including zero).
Connect the relay as shown in Figure 6–2: DIAC 66K TOC INVERSE TIME TEST SETUP on page 6–4. Set the instantaneous unit pickup to 2 Amps (for the 5 Amp rated relay) or 0.4 Amps (for the 1 Amp rated relay) with a zero IOC delay setting.
40.0 to 160.0 PARALLEL 25.0 † 600.0 † Higher currents I may be applied for shorter lengths of time t in accordance with the formula: , K = constant ------- - DIAC Type 66K Digital Overcurrent Relay GE Power Management...
6.11 SERVICING If the relay fails to perform as specified in this instruction manual consult the factory or call your local GE sales office. Before returning the relay consult with the GE Power Management technical support.
Page 48
6 ACCEPTANCE/PERIODIC TESTS GEK-106261 Figure 6–4: REAR, FRONT, AND TOP VIEWS OF THE DIAC TYPE 66K INTERIOR DIAC Type 66K Digital Overcurrent Relay GE Power Management...
Page 49
GEK-106261 6 ACCEPTANCE/PERIODIC TESTS Figure 6–5: DIAC 66K FRONT AND REAR VIEWS GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Page 50
6 ACCEPTANCE/PERIODIC TESTS GEK-106261 DIAC Type 66K Digital Overcurrent Relay GE Power Management...
Page 51
5 5 6 7 8 5 5 6 7 6 7 8 1AMP Model Figure 7–1: BURDEN CURVE BURDENS: 0.1A / 0.5 A unit 0.45 VA 1.0A / 5.0 A unit 2.6 VA GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Page 52
Per IEC 60255-22-3 ELECTROSTATIC DISCHARGE Per IEC 60255-22-2 NOTE: The DIAC Type 66K relay must be powered up at least once per year to avoid deterioration of electrolytic capacitors and subsequent relay failiure. DIAC Type 66K Digital Overcurrent Relay GE Power Management...
Page 53
ADDITION/CHANGE GEK-106261B (to GEK-106261C) cover Updated GE contact information and manual part number. Moved warning concerning electrolytic capacitor deterioration to the SPECIFICATIONS chapter. Updated Figure 4-2 to reflect the correct taps for 2 A and 0.2 A. GE Power Management...
Page 54
A.1 CHANGE NOTES APPENDIX A DIAC Type 66K Digital Overcurrent Relay GE Power Management...
Page 55
66 LONG TIME TOC CURVES ........2-7 FRONT VIEW .............. 1-1 75 SHORT TIME TOC CURVES ........2-8 FRONT VIEW OF DIAC 66K ......... 6-9 77 TOC CURVES ............2-9 FUNCTIONAL BLOCK DIAGRAM ......... 1-2 95 SHORT TIME TOC CURVES ......... 2-10 HANDLING ..............
Page 56
RATINGS ..............2-2, 7-2 55 short time ..............2-5 RATINGS OF TARGET AND SEAL-IN COIL ....2-2 57 medium time ............2-6 REAR VIEW OF DIAC 66K ........... 6-9 66 long time ...............2-7 RECEIVING ..............4-3 75 short time ..............2-8 RESET TARGETS ............4-3 95 short time ............
Page 57
NOTES GE Power Management DIAC Type 66K Digital Overcurrent Relay...
Page 58
GE POWER MANAGEMENT WEBSITE The latest product information for the DIAC 66K relay is available on the Internet via the GE Power Manage- ment home page: JVVRYYY)'KPFWUVTKCNEQORO This site provides access to the following customer services: • Digital Products Directory •...
Page 59