Natural Gas Installation (Typical) - Generac Power Systems G007144 Installation Manuallines

50 hz air-cooled generator sets
Hide thumbs Also See for G007144:
Table of Contents

Advertisement

Fuel Conversion / Gas Connections

Natural Gas Installation (Typical)

NG Megajoules/h = m
A
Fuel data decal
B
Minimum distance from rear obstruction—see Distance Requirements
Manual fuel shutoff valve (pressure port optional)
C
Must be located no more than 1.83 m (6 ft) away from fuel inlet
D
Pipe fittings
E
Flexible fuel line
Verify clearance with gas provider. Regulator should be a minimum of 1.5 m
F
(5 ft) from generator set. Local codes and regulator manufacturer may have fur-
ther clearance requirements.
G
Size gas meter for generator set operating at FULL load plus all appliance loads
H
For underground installations, verify piping system for code compliance
I
Reinforcing rod with clamps
J
To gas main
28
A
D
E
3
/h X 37.26
Figure 5-7. Natural Gas Installation (typical)
F
I
C
B
Installation Guidelines For 50 Hz Air-Cooled Generator Sets
G
H
J
3
BTU/h = ft
/h X 1000
008965