11. Installation Instruction

11.1 Select the Best Location

11.1.1
Indoor Unit
Do not install the unit in excessive oil fume area
such as kitchen, workshop and etc.
There should not be any heat source or steam
near the unit.
There should not be any obstacles blocking the air
circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
Installation height for indoor unit must be at least
2.5 m.
11.1.2
Outdoor Unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
Piping size
Horse
Model
Power
Length
(HP)
Gas Liquid
12.7
6.35
C12***
1.5HP
mm
mm
(1/2")
(1/4")
Example: For C12***
If the unit is installed at 10 m distance, the quantity of
additional refrigerant should be 25 g .... (10-7.5) m x
10 g/m = 25 g.
Addi-
Min.
Max.
Std.
Max
tional
Piping
Piping
Eleva-
Refri-
Length
Length
(m)
tion (m)
gerant
(m)
(m)
(g/m)
5
15
3
20
11.1.3
Piping direction
Right
Right
Rear
Right
bottom
50 mm
or more
This illustration is for explanation purposes only.
Piping
Length
The indoor unit will actually face a different way.
for add.
gas (m)
10
7.5
18
Indoor/Outdoor Unit Installation
Diagram
Attention not to bend
(Front side)
up drain hose
Left
Left
Rear Left bottom
(Left and right are identical)
Insulation of piping connections
• Carry out insulation after
checking for gas leaks and
secure with vinyl tape.
Vinyl tape
Attaching the remote control holder to the wall
Remote control holder fi xing screws 6
Remote
control 3
Remote control holder 5
Floor
It is advisable to avoid
more than 2 blockage
directions. For better
ventilation & multiple-
outdoor installation,
please consult
authorized dealer/
specialist.
Installation parts you
should purchase ( )
Installation plate 1
Bushing-Sleeve ( )
Sleeve ( )
Putty ( )
(Gum Type Sealer)
Bend the pipe as
closely on the wall as
possible, but be careful
that it doesn't break.
Power supply cord ( )
( )
Vinyl tape (wide)
• Apply after carrying
out a drainage test.
• To carry out the
drainage test,
remove the air fi lters
and pour water into
the heat exchanger.
Saddle ( )
Connection cable ( )
Liquid side piping ( )
Gas side piping ( )
Additional drain hose ( )
Control Board cover