The voltage of a single cell of a single battery block is not dangerous. However, a number of cells or
battery blocks, connected in series, can produce hazardous voltages.
· The battery is a "hermetic" type battery and must not be kept in storage or disuse for periods exceeding 6
months at 68°F (20°C) without being recharged (having been charged to 100% at the beginning of any
such period). If this period is exceeded it is essential that the batteries be recharged, which requires that the
UPS be switched on. If these conditions are not respected the performance of the battery can no l longer be
guaranteed. We advise recharging the batteries at least once every 4 months.
· Since new batteries often do not provide full capacity after an initial charge it may be necessary to carry
out a number of discharge/recharge cycles before optimum performance is achieved.
· In order to protect the environment batteries must be disposed of in accordance with the regulations
governing disposal of toxic and harmful waste.

1-7. Repackaging

To re-pack, proceed as follows:
1. Do not pack the equipment until at least six hours have elapsed since the last recharge.
2. Place the equipment in bags made of a material sufficiently porous to allow it to breath (e.g. 100µm
polyethylene).
3. Do not remove air from the packaging.

1-8. About the Operating Instructions

This manual contains information regarding the installation, operation and use of the Uninterruptible Power Supply
(UPS). It is advised that this instruction manual be consulted before installation of the equipment, which operation
shall only be carried out by qualified personnel. Thereafter, it shall be kept and referred to whenever it is necessary
to carry out work on the UPS.