5.0 Emergency Power Off (EPO)

The external connection to the EPO circuit is located just above the USB connector in the upper rear of the unit.
If the circuit between the two EPO connector pins is "opened" the output of the UPS is immediately switched off.
To restart the UPS, the procedures outlined in the section "Single UPS Operation" must be followed. The EPO
circuit may be extended by connecting the "normally closed" switches in series between the EPO connector pins.
Activating (opening) any of the series switches will cause the UPS to shut off its output.
fdfefd fd
© 2019 AMETEK Electronic Systems Protection | Technical Support: 1-800-645-9721 | surgex.com
User Manual
34