3. OPERATIONS

3-1. Operating Mode/Status Description

Mode/Status
Description
UPS Power On
When UPS is powered on, it will enter into this mode for a few seconds for initializing
the system.
AC Mode
When the input voltage is within acceptable range, and the UPS is turned on (the in-
verter is running), the UPS will provide pure and stable sine wave AC voltage. The
UPS will also charge the battery in AC mode.
Converter Mode
When input frequency is within 46 to 64Hz, the UPS can be set with a constant output
frequency (50 Hz or 60Hz) through the inverter. The UPS will still charge battery at
this mode. There is no bypass at this mode.
Battery Mode
When the input voltage is out of the acceptable range or power failure, and the UPS is
turned on (the inverter is running), the UPS will backup power from battery.
Bypass Mode
When input voltage is within acceptable range and the bypass is enabled, and the UPS
(inverter) is not turned on or the inverter can't support the load, the UPS will supply
power to the load through bypass.
Battery Test Mode
When the UPS is in AC mode or Converter mode, and the battery test command is
enabled through LCD or monitoring software, the UPS will start Battery test. This
operation is used to check the battery status.
Warning Status
If some error occurs in the UPS (but is still running normally), the buzzer will alarm
and warning code will appear in the LCD for troubleshooting.
Fault Mode
When fatal error occurs in the UPS, it will beep continuously and go to fault mode.
It will display fault codes in LCD.