2-3-3. Cable Sizes and Current

following table indicates the recommended sizes of conductors in accordance with the NEC®.
The
(air temperature surrounding the conduits not greater than 104°F (40°C).)
NOTE: Cable sizes are suggested and based on standard configurations. Installed input/output wiring for the UPS
should be able to withstand over 40 amps of current. Installers should verify correct conductor sizes and
temperature ratings pursuant to NEC® and/or state or local codes. If the installation requires long conductor runs,
consult NEC® and/or state or local codes to account for electrical losses.
Table 5
Term ID
Input
L
Mains
N
GND
Output
L
N
GND

2-3-4. Connection Warnings

WARNING: Carefully read the following safety notices!
· There is feedback protection inside.
· The UPS should be connected with TN earthing system.
· The power supply for this unit must be single-phase rated in accordance with the equipment nameplate.
It must also be suitably grounded.
· Use of this equipment in life support applications where failure of this equipment can reasonably be
expected to cause failure of the life support equipment or to significantly affect its safety or effectiveness
is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with
air, oxygen, or nitrous oxide.
fdfefd fd
© 2019 AMETEK Electronic Systems Protection | Technical Support: 1-800-645-9721 | surgex.com
Description
Wire gauge
(awg)
Input Line
6
Input Neutral
6
Input Ground
6
Output Line
6
Output Neutral
6
Output Ground
6
User Manual
UPS Part Number
UPS-17602-52R
Term torque
min wire temp
(in - lbs.)
(°C)
10
70
10
70
10
70
10
70
10
70
10
70
12