Page 2
IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS 1) Read these instructions. 10) Protect the power cord from being walked on or pinched particularly at plugs, 2) Keep these instructions. convenience receptacles, and the point 3) Heed all warnings. where they exit from the product. 4) Follow all instructions.
- Signal present RoHS compliant • Covered by Biamp Systems’ warranty The Vocia software provides the interface for configuring and programming the VA-4030(e) and VA-2060(e) amplifiers. The information supplied by this manual relates to hardware installation, physical connections and device and channel failover concerns. For more details...
VOCIA AMPLIFIERS VA-2060, VA-2060e, VA-4030, VA-4030e FRONT PANEL System Indicators The LED indicators on the front panel of the amplifier provide information and operational status of the amplifier and its associated output and input channels. LED layout and features vary between amplifier models. LEDs are grouped to show chassis and amplifier channel status indication.
VOCIA AMPLIFIERS VA-2060, VA-2060e, VA-4030, VA-4030e FRONT PANEL Channel Indicators Amp Channel Indicators These indicators relate to each amplifier channel: Amp Fault is a yellow LED that illuminates when a channel fault has occurred. Two types of channel faults can be reported depending on the severity of the problem.
VOCIA AMPLIFIERS VA-2060, VA-2060e, VA-4030, VA-4030e REAR PANEL Rear Panel BIAMP SYSTEMS CAUTION assembled in the USA RISK OF ELECTRICAL SHOCK. 0832-CPD-1401 N24138 DO NOT OPEN. www.biamp.com 52SJ Model VA-4030e Analog Inputs Outputs 8Ω 8Ω 8Ω 8Ω 4Ω 100V 4Ω...
VOCIA AMPLIFIERS VA-2060, VA-2060e, VA-4030, VA-4030e REAR PANEL Table 1. CobraNet LED indication Left LED Right LED Description None None No data connectivity or CobraNet activity None Flashing Green Link Established. Typically seen on Secondary connection that is in standby. Amber Flashing Green Link established and CobraNet activity detected;...
VOCIA AMPLIFIERS VA-2060, VA-2060e, VA-4030, VA-4030e REAR PANEL Amplifier Output Connections CAUTION: All speaker wiring connections and output load selection should be made by qualified personnel and with the amplifier power removed. The 100V output requires Class 3 wiring. Please refer to a qualified electrician or other qualified person according to local codes. Transformer Load Selection The required amplifier output load is configured via the use of a recessed indented selector above the amplifier speaker output connectors.
VOCIA AMPLIFIERS VA-2060, VA-2060e, VA-4030, VA-4030e REAR PANEL Output Fault Detection The Amplifier monitors (supervises) for faults on speaker connections using a combination multiple out-of-band (inaudible) high frequency tones for end-of-line detection, and DC current for ground fault detection. For end-of-line detection, one or more (up to 15 maximum) ELD-1 units must be connected to the end/s of the speaker line.
VOCIA AMPLIFIERS VA-2060, VA-2060e, VA-4030, VA-4030e FAILOVER MODES Failover Modes The Vocia amplifiers support a device-to-device or channel-to-channel failover mode. Only one type of failover mode can be implemented per amplifier. Device-to-Device Failover All amplifiers support device-to-device amplifier chassis failover in case of fault. The redundant amplifier must be the same model as the primary amplifier.
VOCIA AMPLIFIERS VA-2060, VA-2060e, VA-4030, VA-4030e FAILOVER MODES Channel-to-Channel Failover All amplifiers support channel-to-channel failover. This is configured in the Vocia software in the amplifiers general setting as 1:1 Failover. In this configuration, channel pairs can be specified and adjacent channels will act as a redundant backup. Channel 2 will act as backup for channel 1.
VOCIA AMPLIFIERS VA-2060, VA-2060e, VA-4030, VA-4030e CURRENT DRAW AND HEAT OUTPUT VA-4030 and VA-4030e Specifications 1/8 POWER 1/3 POWER FULL POWER IDLE PINK NOISE PINK NOISE SINE WAVE Total Output Channels Input Power BTU /hr Input Power BTU /hr Input Power BTU /hr Input Power BTU /hr...
9. BIAMP Systems shall not be liable for special, indirect, incidental, or consequential damages, including lost profits or loss of use arising out of the purchase, sale, or use of the products, even if BIAMP Systems was advised of the possibility of such damages.
FCC COMPLIANCE FCC NOTICE - CLASS B DIGITAL DEVICE NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential as well as in a commercial installation.
DIRECTIVES below except as noted herein. Any alterations to the product not agreed upon and directed by Biamp Systems Corporation will invalidate this declaration. ® Product Models:...
Page 20
COMPLIANCE RoHS COMPLIANT This Biamp product, including all attendant cables and accessories supplied by Biamp, meets all requirements of EU Directives 2002/95/EC of January 27, 2003, and 2005/618/EC of August 18, 2005, the EU RoHS Directives. An EU RoHS Materials Content Declaration document may be obtained at www.biamp.com...
Need help?
Do you have a question about the Vocia VA-2060 and is the answer not in the manual?
Questions and answers