COOL / DRY/HEAT Model This air conditioner uses the new refrigerant R410A. Contents Model Combinations Page Indoor Units IMPORTANT! AWMI28AHL Please Read Before Starting ........1 AWMI36AHL AWMI50AHL GENERAL ............2 AWMI70AHL 1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit Outdoor Unit 1-3.
IMPORTANT! Please Read Before Starting When Installing… This air conditioning system meets strict safety and oper- ating standards. As the installer or service person, it is an …In a Ceiling or Wall important part of your job to install or service the system Make sure the ceiling/wall is strong enough to hold the so it operates safely and efficiently.
Cut each tube to the appropriate lengths +30 cm to 40 cm to dampen vibration between units. Table 2 Narrow Tube Wide Tube Model Outer Dia. Thickness Outer Dia. Thickness AWMI28AHL 6.35 mm 0.8 mm 9.52 mm 0.8 mm AWMI36AHL 6.35 mm 0.8 mm 9.52 mm 0.8 mm AWMI50AHL 6.35 mm...
1-5. Additional Materials Required for Installation (1) Refrigeration (armored) tape (2) Insulated staples or clamps for connecting wire (See local codes) (3) Putty (4) Refrigeration lubricant (5) Clamps or saddles to secure refrigerant tubing 2. Installation Site Selection 2-1. Indoor Unit To prevent abnormal heat genera- WARNING tion and the possibility of fire, do...
Page 5
In the case below, a joint for connecting tubes of different sizes is needed when connecting the inter-unit tube (φ9.52) to the outdoor unit valve (φ12.7). (1) Connecting indoor unit types 28 to 36 at D Indoor unit Outdoor unit φ6.35 (28 36 types) φ9.52...
2-2. Outdoor Unit Exhaust fan AVOID: Hot air heat sources, exhaust fans, etc. (Fig. 3) Heat source damp, humid or uneven locations. Outdoor unit choose a place as cool as possible. choose a place that is well ventilated. allow enough room around the unit for air intake/ Fig.
Outer Dimensions of 2-3. Outdoor Unit Service valve on narrow tube side (Outer diameter φ6.35) Service valve on wide tube side (Outer diameter φ9.52) Service valve on wide tube side (Outer diameter φ12.7) Fig. 5 Diagram of Outdoor Unit Installation 2-4.
3. Installation Process Embedding the Tubing and Wiring 3-1. Do not connect tubes to locations that are embedded. Be sure to bind refrigerant tubing and inter-unit cables together with vinyl tape. The power cable must be obtained on-site. (φ2.0: Less than 15 m / φ2.6: Less than 20 m / φ3.5: Less than 26 m) Be sure to apply the provided labels to both ends of the inter-unit cables to prevent miswiring.
NOTE Copper When reaming, hold the tube end downward and be tubing sure that no copper scraps fall into the tube. (Fig. 8) (3) Remove the flare nut from the unit and be sure to Reamer mount it on the copper tube. (4) Make a flare at the end of copper tube with a flare tool.* (Fig.
Torque wrench Be sure to match refrigerant CAUTION tubing and electric wiring between indoor and outdoor Spanner Indoor unit units. For more details, refer to “Tubing Check Control” in the Technical & Service Manual. Outdoor unit Fig. 14 3-7. Insulation of Refrigerant Tubing IMPORTANT To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated...
3-10. Refrigerant Operation System When the air conditioner is turned ON, the compressor starts to work. The compressor absorbs low-temperature and low-pressure refrigerant from the evaporator; the refrigerant is then compressed into high-temperature and high- pressure refrigerant gas and goes into the condenser (COMPRESSION). This high-temperature and high-pressure refrigerant gas is condensed into liquid refrigerant;...
4. Air Purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. There- fore, they must be purged completely. pressure in the system rises operating current rises Service Manifold gauge valve on cooling efficiency drops (special for R410A) narrow High-pressure valve...
Page 13
(4) With the “Lo” knob of the manifold valve open and high-pressure valve (“Hi”) closed completely, run the vacuum pump. Run the pump until the pres- sure is –101 kPa (–76 cmHg). The operation time for the vacuum pump varies with tubing length and the capacity of the pump.
(11) Replace the flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench. Next, mount the valve cap and tighten it with a torque wrench (the cap needs to be tightened with the torque of 200 kg-cm).
(3) Perform cooling operation or forced cooling operation. When the pressure at the low-pressure side is 0.15 – 0.2 MPa (0.5 – 1 kg/cm G), fully close the Wide tube side spindles at the valves on the wide tube side of tubes A, B, C, and D, and immediately stop oper- ation.
5-2. Recommended Wire Length and Diameter Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local elec- trical codes. Carefully observe these regulations when carry- ing out the installation. Table 7 shows maximum wire lengths for control line and power line and fuse or circuit capacity.
5-4. Electric Wiring Diagram INDOOR UNIT AWMI28AHL Inter-unit cables Terminal board W(BK) heat exchanger Room temperature Flap motor sensor Heat exchanger temperature sensor Fan motor BK (ORG) Humidity sensor BK (ORG) Control panel Display/ receiver panel (GRN) (GRN) Black White...
Page 19
Electric Wiring Diagram for 4-room-multi outdoor unit (AE4MI91AH) Before replacing PCBs, turn off the power and check that all CAUTION lamps on the PCB are off before starting work. Electric shock will occur if work is performed while the lamps are lit. Electric Shock Fig.
5-5. How to Connect Wiring to the Terminal Loose wiring may cause the WARNING terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected. When connecting each power wire to the correspond- ing terminal, follow the instructions below and fasten 7 mm (ACTUAL STRIP...
5-6. Wiring Instructions for the Outdoor Unit CAUTION Be sure to correctly align inter-unit cables A, B, C and D. Outdoor unit A Attach the label Terminal board 3 1 2 3 4 5 6 7 8 3 4 5 6 7 8 Indoor unit A BK W BKW R...
6. Test Run Performing a test run Refer to the test run procedures in the indoor unit installation manual. Perform the test run separately for each connected indoor unit. If 2 units are operated simultaneously, it is not possible to correctly check for errors in tubing and wiring.
7. Installation Check Sheet The strength of the installation location is sufficient to support the A/C weight. The indoor and outdoor units are installed level and vertically. The power and voltage are as specified. Inter-unit cables are securely fastened to the termi- nal board.
Page 24
COP-INVERTER-ARGO.qxd 6-02-2004 16:07 Pagina 2 Via Varese, 90 - 21013 Gallarate - Va - Italy Tel. +39 0331 755111 - Fax +39 0331 776240 www.argoclima.it...