External Demand Via 0 - 10 V Input; External Blocking Via Switching Contact - Viessmann Vitocrossal 100 Installation Instructions For Contractors

Gas condensing boiler with matrix cylinder burner open flue and room sealed operation fully pre-assembled and wired
Table of Contents

Advertisement

Boiler electrical connection
Plug
lH
A
1 L
N
?
lH
Floating contact (when connected, remove jumper
A
between L and 1)
Codes
"4b:1" in group "General"/1
Effect of the function on the relevant heating circuit
pump:
coding address "d7" in group "Heating circuit" (only
for weather-compensated control units)
Effect of the function on the circulation pump for cylin-
der heating:
coding address "5F" in group "DHW"/3
External demand via 0
Connection at 0
10 V input at EA1 extension.
Ensure DC separation between the earth conductor
and the negative pole of the on-site power source.
[{{]
aBJ
f-]
0-10V
+ -
S P
Ö
L
U
+
Fig. 30

External blocking via switching contact

Connection options:
Plug
lH
EA1 extension (accessory, see separate installation
instructions)
(cont.)
10 V input
A
N
N
L
EA1 extension
[{A
[{S
DE
DE
A
Floating contact
A
EA1 extension
B
Codes
Set "3A" (DE1), "3b" (DE2) or "3C" (DE3) to 2 in
group "General"/1
Effect of the function on the relevant heating circuit
pump:
coding address "d7" in group "Heating circuit" (only
for weather-compensated control units)
Effect of the function on the circulation pump for cylin-
der heating:
coding address "5F" in group "DHW"/3
0 to 1 V
No specification for set boiler water
temperature
1 V
Set value 10 °C
10 V
Set value 100 °C
When the contact is closed, the burner is switched off.
The heating circuit pump and (if installed) the circula-
tion pump for cylinder heating are switched according
to the set code (see the following table "Codes").
B
[{D
DE
27