External Demand Via 0 - 10 V Input; External Blocking Via Switching Contact - Viessmann VITOCROSSAL Installation Instructions Manual

80 to 318 kw. gas condensing boiler with matrix cylinder burner. open flue and room sealed operation
Table of Contents

Advertisement

Connecting external cables
Plug
lH
A
1 L
N
?
lH
Floating contact (when connecting, remove jumper
A
between L and 1)
Parameters/codes
"4b:1" in the "General"/1 group
Effect of the function on the relevant heating circuit
pump:
Parameter/coding address "d7" in the "Heating cir-
cuit" group (only for weather-compensated control
units)
Effect of the function on the circulation pump for cylin-
der heating:
Parameter/coding address "5F" in the "DHW"/3
group
External demand via 0
Connection at 0
10 V input at EA1 extension.
Ensure DC separation between the earth conductor
and the negative pole of the on-site power source.
[{{]
0-10V
aBJ
f-]
+ -
S P
Ö
L
U
+
Fig. 38

External blocking via switching contact

Connection options:
Plug
lH
EA1 extension (accessory, see separate installation
instructions)
(cont.)
10 V input
A
N
N
L
EA1 extension
[{A
[{S
DE
DE
A
Floating contact
A
EA1 extension
B
Parameters/codes
Set "3A" (DE1), "3b" (DE2) or "3C" (DE3) to 2 in the
"General"/1 group
Effect of the function on the relevant heating circuit
pump:
Parameter/coding address "d7" in the "Heating cir-
cuit" group (only for weather-compensated control
units)
Effect of the function on the circulation pump for cylin-
der heating:
Parameter/coding address "5F" in the "DHW"/3
group
0 to 1 V
No specification for set boiler water
temperature
1 V
Set value 10 °C
10 V
Set value 100 °C
When the contact is closed, the burner is switched off.
The heating circuit pump and (if installed) the circula-
tion pump for cylinder heating are switched according
to the set parameter/code (see the following table
"Parameters/codes").