Section 4 Preventative Maintenance; Periodic Inspection - L.B. White AW060 Installation And Service Manual

Hot surface ignition
Table of Contents

Advertisement

1. The a a rea s s urrounding t t he h h eater s s hall b b e k k ept c c lear
and f f ree f f rom c c ombustible m m aterials, g g asoline, a a nd
other f f lammable v v apors a a nd l l iquids.
2. Have your gas supplier check all gas piping annually
for leaks or restrictions in gas lines. Also, at this time
have your gas supplier clean out the sediment trap of
any debris that may have accumulated.
3. Regulators must be periodically inspected to make
sure the regulator vents are not blocked. Debris,
insects, insect nests, snow, or ice on a regulator can
block vents and cause excess pressure at the
appliance.
4. Regulators can wear out and function improperly.
Have your gas supplier check the date codes on all
regulators installed and check delivery pressures to
August 1999
the appliance to make sure that the regulator is
reliable.
5. Check all wiring associated terminals and electrical
components within the heater for corrosion, frayed or
cut insulation, tight connections, etc.
replace as necessary.
6. Review all heater markings (i.e. wiring diagrams,
warnings, start-up, shut-down, troubleshooting, etc.)
at the time of maintenance for legibility. Make sure
none are cut, torn, or otherwise damaged.
damaged markings must be replaced immediately.
Contact the L.B. White Co. for replacement markings.
Dataplates, start-up and shut-down instructions and
warnings are available at no cost. A nominal charge
will
be
applied
for
troubleshooting markings.
Preventative
Maintenance

Periodic Inspection

Repair or
Any
wiring
diagrams,
and
4.1-1 1