Further details regarding the individual steps
8. Check the function of the neutralising
system (if installed), including the
hydraulic seal in the siphon.
Neutralising system operating
instructions

Reducing operational output (if necessary)

The maximum operational output of the burner can be set to between 70 and
100 % if necessary.
C
D
E
F
Status
Service
C
D
R
S
E
F
Commissioning, inspection, maintenance
9. Check all gaskets and plugs, and
retighten if necessary.
Note
We recommend you check all con-
nections on the heating water side for
leaks approx. every 500 hours.
1. Press button S E for longer than 2 s.
" " flashes.
2. Press button
shows "6" under Service.
3. Press button S E. In display C,
"6" appears under Status.
4. Press button S E. "1" will be dis-
played under Status in display C
and the current value for the maxi-
mum operational output is shown in
% under Service.
5. Press button
required maximum operational out-
put.
G
6. Press button S E to confirm. If
applied successfully, "1" will be
shown in display C under Service,
or "0" will appear if it failed.
7. Press button S E to switch to the
operating display.
8. Press button R G.
The system will be restarted.
(cont.)
F until display C
F or
D for the
15