Burner control unit
Burner control unit
Resetting operating parameters to their delivered condition
To reset all operating parameters to their
delivered condition, press the following
keys:
1. S longer than 2 s, " " flashes.
2.
until "6" is shown under Service.
3. S "6" will be displayed under Sta-
tus.
Manual mode and service display
The burner must be running to call up the service display and for manual mode. The
service display shows the current modulation level in %.
Hold down the following keys:
1.
/S simultaneously for longer than
2 s.
The burner changes to manual
mode, a "P" will be shown
under Status and the current
modulation level will flash
under Service.
2.
for lower heating output,
until "0" is shown under Serv-
ice.
3.
for upper heating output,
until "100" is shown under Serv-
ice.
4.
/S simultaneously for longer than
2 s.
The burner returns to modulat-
ing mode.
46
(cont.)
4.
5. S "1" is shown under Status and
6. S to confirm. If reset successfully,
7. S to change to the operating dis-
until "0" is shown under Service.
"dEL" under Service.
"1" will be shown under Service; if
it failed, "0" will appear.
play.