2.6
WISE-4050
2.6.1
I/O Specification
Digital Input
–
Channel: 4
–
Logic level
–Dry Contact 0: Open
–Wet Contact 0: 0~3 V
–All 4 channels should be configured to dry contact or wet contact in the
same time
–
Isolation: 3,000 V
–
Supports 32-bit Counter Input Function (Maximum signal frequency 3 kHz)
–
Keep/Discard Counter Value when Power-off
–
Supports Frequency Input Function (Maximum frequency 3 kHz)
–
Supports Inverted DI Status
Digital Output
–
Channels: 4
–
Open collector to 30 V, 500 mA max. for resistance load
–
Inductive loads require an external diode to eliminate back-EMF when the
DO is turned off
–
Isolation: 3,000 V
–
On Resistance (R
–
Supports 5 kHz Pulse Output
–
Supports High-to-Low and Low-to-High Delay Output
WISE-4000 User Manual
1: Close to DI COM
DC
1: 10~30 V
(3 mA min.)
DC
rms
rms
): 0.7 Ω (max.) @ 500mA, 25°C
DS(ON)
24