ABB PGX100 Operating Instruction page 25

Gauge and absolute pressure transmitters
Table of Contents

Advertisement

P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C
. . .8 Error messages
. . .Error states and alarms
HMI -
Code
Error
NAMUR
Code
F
102.004
P-dP out of
limits
F
098.034
Analog
output
saturated
S
054.006
Sensor
temperature
out of limits
S
052.031
Max working
pressure
exceeded
C
090.033
Loop test
C
080.030
Input
simulation
active
Description
The measured Pressure value is outside
the sensor limits and no longer
representing the true applied pressure
The analog output (4 to 20 mA) is frozen
to one of its Saturation limits between
High or Low and no longer represents the
true applied process.
This is not a device error, but it is
consequence of its configured working
range in relation to the dynamic of the
process measurement.
The sensor temperature is outside its
operational limits as specified in the
product data-sheet.
This is not a device issue but if its sensor
is subject to work at abnormal
temperature conditions for long time,
then the device components could
degrade affecting its accuracy and
reliability.
The measured process pressure is higher
than the acceptable mechanical limit of
the process connection elements.
When this condition occurs, there is the
risk to damage the transmitter and to be
dangerous for the personnel.
The 4 to 20 mA signal in output by the
transmitter is simulated by the user and
no longer represents the true applied
At least one of the following variables
produced by the transmitter is simulated
and doesn't represent the real calculated
1. the pressure value
2. the Sensor temperature value
3. the Scaled output value.
Possible cause
The measurement range has not
been correctly calculated OR an
incorrect transducer model has
value.
been selected.
The applied/measured pressure
is beyond the configured working
range represented by the Low and
High range values.
The temperature of the process
environment affects the pressure
In some situation, the device
installation could be the cause of a
sensor overheating.
The selected transmitter and/or
the process connection elements
are not adequate for the specific
process conditions.
The operator could have enabled
the loop test function in order to
simulate the current output for
process.
testing purposes but, at the end,
forgot to return it back to normal
condition disabling the loop test
The operator could have enabled
the input simulation of one or
more device variables for testing
value:
purposes but, at the end, forgot to
return it back to normal condition
disabling the input simulation
Suggested action
The compatibility of
pressure transmitter
model and process
conditions has to be
checked. Probably a
different transmitter
type is required.
Use a HART
configurator
(DD handheld) in order
1. Recognize in detail at
which limit (high or low)
the analog output is
Saturated
2.Adjust the Saturation
Limit or the working
range if possible.
The compatibility of
pressure transmitter
transmitter;
model and process
conditions has to be
checked.
It could be required to
perform a new sensor
trimming or device
replacement.
A different installation
type could be also
considered/ required
e.g. use of remote seals.
The compatibility of the
pressure transmitter
model with process
conditions must be
checked and, if
necessary, replace the
instrument with
another having the
correct characteristics.
Use a HART
configurator
(DD handheld) to place
device back into normal
operating mode
(disable the analog
function.
output simulation).
Use a HART
configurator
(DD handheld) in order
1. recognize in detail
which variable is under
condition.
simulation condition
2. place device back into
normal operating mode
(disable the input
simulation).
Otherwise just power
off/on the device in
order to disable the
input simulation.
25
Tx
Response
No effect
No effect
to:
No effect
No effect
No effect
No effect
to: