Pilot Flame Characteristics; Main Burner Flame Characteristics - Empire Heating Systems DVC55SPPXLP-1 Installation Instructions And Owner's Manual

Fan type direct vent wall furnace
Table of Contents

Advertisement

Available languages

Available languages

The correct pilot flame (Figure 11) will be blue, extending past
the thermocouple. The flame will surround the thermocouple just
below the tip.
Natural gas pilots require adjusting when the inlet gas pressure is
above 5" w.c. Remove the pilot cover screw on the control valve
(Figure 3, page 8), and turn the adjustment screw clockwise to
reduce flame. Replace pilot cover screw to eliminate gas leaking
at that control valve opening.
LP gas (propane) will not require adjustment.
After use, cleaning may be required for the proper flame.

MAIN BURNER FLAME CHARACTERISTICS

The correct flame will be a short blue inner flame with a much larger
light blue outer flame. The main burner (Figure 12) shows the ap-
proximate height of each part of the flame for each gas. The burner
does not have a primary air adjustment. The flame will be correct
if the factory-set pressure and orifice opening are used. After the
furnace has been operating, the burner ports may be blocked by
foreign matter carried in by combustion air. Therefore, cleaning of
the burner may be needed for proper flame.
To clean burner port disconnect the gas supply to the valve, and
remove the eight screws fastening the burner door. after removing the
burner door from the combustion chamber, remove rear burner, pilot
burner and front burner. With front and rear burners removed from
furnace, force water into the ribbon ports and dry with air pressure.
32188-0-0616

PILOT FLAME CHARACTERISTICS

PROPER FLAME ADJUSTMENT
Figure 11