Viessmann Vitoflame 100 Service Instructions For Contractors page 50

Pressure-jet gas burner for vitoplex 100, 200 and 300 rated output 80 to 225 kw for vitorond 200 rated output 125 to 195 kw
Hide thumbs Also See for Vitoflame 100:
Table of Contents

Advertisement

Specification
Standard values for burner settings
Gas
Operational net
group
calorific value
H
uB
3
kWh/m
MJ/m
Natural
8.13
29.25
gas LL
Note
Partial load gas throughput equals 60 % of the full load gas throughput.
In conjunction with the Vitorond 200
Nozzle pressure table and mixing assembly settings
Gas
Wobbe
group
index Wo
kWh/
MJ/
3
3
m
m
Natural
15.00 54.00 20.0
gas E
Natural
12.40 44.60 20.0
gas LL
Standard values for mixing assembly
settings
*1
1 mbar equals nearly 10 mm WS; e.g. 12.0 mbar
The nozzle pressures apply to 15 ºC, 1013 mbar, dry.
50
(cont.)
3
3
Gas
m
/h
throu-
ghput
litres/
min
Supply
pres-
sure
*
1
mbar
Nozzle
Stage
pres-
1
sure
Stage
2
*
1
mbar
Nozzle
Stage
pres-
1
sure
Stage
2
*
1
mbar
mm
120 mm WS.
Rated boiler output
90 kW
120
150
kW
kW
12.0
16.0
20.0
200
264
334
Rated boiler output
125
160
kW
kW
2.1
2.8
5.3
6.9
2.7
3.4
6.3
8.1
14.0
17.0
200
kW
26.7
446
195 kW
3.0
7.0
4.0
9.0
14.0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vgiii

Table of Contents