Viessmann Vitoflame 100 Service Instructions For Contractors page 31

Pressure-jet gas burner for vitoplex 100, 200 and 300 rated output 80 to 225 kw for vitorond 200 rated output 125 to 195 kw
Hide thumbs Also See for Vitoflame 100:
Table of Contents

Advertisement

Diagnosis
(cont.)
Fault
Flash-
ing
code
red
Burner starts,
flame builds, but
the system shuts
down after a short
while (not a fault
shutdown)
Burner goes from
7 ×
operation into a
fault state, when
flame is already
established
7 ×
7 ×
7 ×
Flame extin-
7 ×
guishes during op-
eration
7 ×
Cause
Lack of gas
Ionisation current too
low (< 1.5 µA)
Electrode body faulty
Ionisation current too
low because of incor-
rect burner settings
Faulty earthing
Mixer assembly con-
taminated
Air damper incorrectly
positioned
Troubleshooting
Measures
Clean or replace gas
filter. Check the gas
pressure switch set-
tings. Check the gas
supply pressure.
Check the position and
condition of the sensor
electrode and modify
or replace the elec-
trode, if required
Measure ionisation
current and replace io-
nisation electrode or
earth electrode, if re-
quired
Correct burner settings
Check the earth con-
nection
Clean mixer assembly
Correct the switch cam
adjustment at the air
damper motor (see
page 8)
31