Standard Values For Burner Settings - Viessmann Vitoflame 100 Service Instructions Manual

Oil pressure jet burner (type ve iii) for vitoplex 100 rated output 90 to 210 kw
Table of Contents

Advertisement

Standard values for burner settings

Please note:
Check that the service instructions are valid for the burner concerned (see
notes on applicability, page 2 and serial no. on the burner type plate).
Rated output
range
Boiler output
Oil burner nozzle
Make Fluidics
Make Steinen
Oil pressure
*1
approx.
Stage 1
Stage 2
Oil flow rate
Stage 1
Stage 2
Switch cam
position at the
air damper
actuator
ST 1
ST 2
MV
Blast connection
setting
*1
The oil pressure may vary from that indicated by the values shown, due to nozzle
tolerances and varying oil characteristics.
from kW
to kW
kW
90
Type
45º H
Type
Gph
1.65
bar min.
10.0
bar
17.5
kg/h
5.8
l/h
6.8
kg/h
8.3
l/h
9.7
º
19
º
38
º
25
mm
8
90
125
100
140
100
125
140
45º S
45º S
45º S
1.75
2.25
2.50
10.0
11.5
9.7
21.0
23.6
20.0
6.4
8.0
9.0
7.5
9.4
10.6
9.2
11.5
12.8
10.8
13.5
15.0
20
24
27
70
70
70
35
35
35
18
13
16
Appendix
150
165
150
165
190
45º S
45º S
45º S
2.50
2.75
3.50
10.5
11.0
9.0
23.5
23.0
18.0
9.6
10.6
12.2
11.3
12.4
14.4
13.7
15.1
17.4
16.1
17.7
20.5
21
25
29
40
55
46
30
35
35
9
10
12
190
210
210
45º S
3.50
11.5
24.0
13.5
15.9
19.3
22.6
29
42
35
16
37