Standard values for burner settings
Please note:
Check that the service instructions are valid for the burner concerned (see
notes on applicability, page 2 and serial no. on the burner type plate).
Rated output
range
Boiler output
Oil burner nozzle
Make Fluidics
Make Steinen
Oil pressure
*1
approx.
Stage 1
Stage 2
Oil flow rate
Stage 1
Stage 2
Switch cam
position at the
air damper
actuator
ST 1
ST 2
MV
Blast connection
setting
*1
The oil pressure may vary from that indicated by the values shown, due to nozzle
tolerances and varying oil characteristics.
from kW
to kW
kW
90
Type
45º H
Type
Gph
1.65
bar min.
10.0
bar
17.5
kg/h
5.8
l/h
6.8
kg/h
8.3
l/h
9.7
º
19
º
38
º
25
mm
8
90
125
100
140
100
125
140
45º S
45º S
45º S
1.75
2.25
2.50
10.0
11.5
9.7
21.0
23.6
20.0
6.4
8.0
9.0
7.5
9.4
10.6
9.2
11.5
12.8
10.8
13.5
15.0
20
24
27
70
70
70
35
35
35
18
13
16
Appendix
150
165
150
165
190
45º S
45º S
45º S
2.50
2.75
3.50
10.5
11.0
9.0
23.5
23.0
18.0
9.6
10.6
12.2
11.3
12.4
14.4
13.7
15.1
17.4
16.1
17.7
20.5
21
25
29
40
55
46
30
35
35
9
10
12
190
210
210
45º S
3.50
11.5
24.0
13.5
15.9
19.3
22.6
29
42
35
16
37