Initial start-up, inspection and maintenance
Further details regarding the individual steps
7. If necessary, adjust the oil
pressure at the pressure
adjusting screw for stage 1 C
and stage 2 D.
Turn clockwise ³ pressure rises
Anti-clockwise ³ pressure falls.
For standard values for burner
settings, see page 37.
8. Check the emission values by
taking actual measurements after
checking the oil pressure.
9. Switch OFF the mains isolator
and safeguard against
unauthorised reconnection.
10. Remove the pressure and
vacuum gauges.
11. Insert plugs "P" A and "V" B.
Check the plugs for damage and
replace if necessary.
12. Start the burner and check the
plugs for leaks.