Viessmann Vitoflame 100 Service Instructions Manual page 10

Oil pressure jet burner (type ve iii) for vitoplex 100 rated output 90 to 210 kw
Table of Contents

Advertisement

Initial start-up, inspection and maintenance
Further details regarding the individual steps
10
(cont.)
Fine adjustment stage 1
1. Set service switch E to position II
(automatic mode), and close the
cover flap.
2. Switch the burner over to stage 1
by pulling plug lÖ.
3. Remove the actuator motor cover.
4. Modify the air volume by turning
the adjusting screw on switching
cams ST 1 (see fig. on page 6):
H Clockwise ³ more air,
H Anti-clockwise ³ less air.
Please note:
Adjust switching cams ST 1 (fine
adjustment) in small steps.
The set value for switching
cam MV must not lie below the set
value of switching cam ST 1 and
not above that of switching
cam ST 2.
After every adjustment of
switching cam ST1, briefly drive
the burner to stage 2 and back
again to stage 1 (connect plug lÖ
and remove again or use the
service plug), to balance out the
switching hysteresis.
5. Fit the actuator motor cover.
6. Check the service plug adjustment.